A-102 — Architectural Reflected Ceiling Plan (Demo)

Demo: Data Center Campus (Full Set) / Rev A / architectural / spec

3 clause(s)

LabelTextPageExtraction method
1.1 1.1 Reflected ceiling plan for Data Hall 1 requires a minimum 9 feet 0 inches clear from finished floor to the underside of any overhead equipment, duct, tray, or pipe. 1 spec_text
1.2 1.2 Reflected ceiling plan for Data Hall 4 requires a minimum 8 feet 6 inches clear from finished floor to the underside of any overhead equipment, duct, tray, or pipe. 1 spec_text
2.1 2.1 Acoustic ceiling tile grid in the office corridor is set at 9 feet 0 inches above finished floor, non-structural. 1 spec_text