| Label | Text | Page | Extraction method |
|---|---|---|---|
| 1 | 1. WH-1 is a 50-gallon gas-fired water heater on an 18" stand, located in Mech/Elec Room 105. It is set 1'-6" (18") clear from the east wall of the room. | 1 | pdf_text |
| 10 | 10. Provide floor drain at Mech/Elec Room 105 per code; route T&P relief discharge and any condensate to this drain. | 1 | pdf_text |
| 2 | 2. Coordinate WH-1's location with the electrical engineer's Panel EP-2, shown on E-101 on the same wall -- EP-2 requires 36" of dedicated clear working space, and WH-1 as located reduces the usable clear floor space in front of that panel to approximately 18". | 1 | pdf_text |
| 3 | 3. The T&P relief valve discharge is piped full-size to within 6" of the floor per the water heater manufacturer's instructions, and directed to the floor drain in Mech/Elec Room 105. | 1 | pdf_text |
| 4 | 4. Restroom 104 (accessible) contains one water closet (3" waste / 2" vent) and one wall-hung lavatory (1-1/2" waste), both ADA compliant. | 1 | pdf_text |
| 5 | 5. A mop sink (3" waste / 2" vent) is provided in Mech/Elec Room 105. | 1 | pdf_text |
| 6 | 6. Each of the four operatories (107, 108, 109, 112) has one clinical hand-wash sink (1-1/2" waste). | 1 | pdf_text |
| 7 | 7. Domestic water piping is Type L copper; waste and vent piping is PVC DWV throughout, unless noted otherwise. | 1 | pdf_text |
| 8 | 8. Verify WH-1 clearance from the east wall against the electrical panel clearance requirements shown on E-101 before setting the unit; see the WH-1 notes above. | 1 | pdf_text |
| 9 | 9. Fixture connection sizes noted above are for planning purposes; confirm final sizing with the plumbing fixture cut sheets during submittal review. | 1 | pdf_text |