CI-6 — P-101 — Plumbing Plan

Riverbend Family Dental Clinic / Rev C / plumbing / pdf_2d

12 clause(s)

LabelTextPageExtraction method
1 1. WH-1: 50-gal. gas-fired water heater, set on 18" stand, located in Mech/Elec Room 105 per plan. 1 pdf_text
1-1 1-1/2"W ADA compliant MS Mop Sink 1 pdf_text
1-1 1-1/2"W Each operatory WH-1 Water Heater, 50-gal gas 1 pdf_text
2 2. WH-1 clearance from east wall shown = 1'-6" (18"); coordinate with Electrical Panel EP-2 dedicated equipment space shown on E-101 (36" min. required per NEC 110.26(A)(1)) -- WH-1 as located reduces available clear floor space in front of EP-2. 1 pdf_text
3 3"W/2"V Mech/Elec Rm. S Sink, clinical hand-wash 1 pdf_text
3 3"W/2"V ADA compliant LAV Lavatory, wall hung 1 pdf_text
3 3/4" CW/HW See note 1-2 1 pdf_text
3 3. T&P relief valve discharge piped full size to within 6" of floor per IPC / manufacturer's instructions. 1 pdf_text
4 4 A B C D VEST. WAITING OFFICE RR MECH/ELEC OPER. 1 OPER. 2 OPER. 3 STERIL. BREAK OPER. 4 STORAGE WH-1 WH-1 SET 1'-6" CLR FROM E. WALL -- VERIFY ELEC. PANEL EP-2 CLEARANCE (E-101) WC LAV MS S S S S PLUMBING GENERAL NOTES 1 pdf_text
4 4. All waste and vent piping PVC DWV; domestic water piping Type L copper, U.N.O. 1 pdf_text
4400 4400 W. City of Ch Permit No Plumb Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE) 1 pdf_text
5 5. Fixture units and pipe sizing per fixture schedule, this sheet. Tag Fixture Conn. Notes WC Water Closet, tank type 1 pdf_text