E-101 — Electrical Switchgear & Panel Layout (Demo)

Demo: Data Center Campus (Full Set) / Rev A / electrical / spec

3 clause(s)

LabelTextPageExtraction method
1.1 1.1 Switchgear SG-2 in Electrical Room 210 requires a dedicated 42 inch deep working clearance, free of any other trade's infrastructure, per NEC 110.26. 1 spec_text
1.2 1.2 Switchgear SG-4 in Electrical Room 214 requires a dedicated 36 inch deep working clearance, free of any other trade's infrastructure, per NEC 110.26. 1 spec_text
2.1 2.1 Panel EP-9 in Data Hall 1 electrical closet is wall-mounted at 5 feet 0 inches above finished floor. 1 spec_text