Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 7
Severity: high
Engine: real / claude-sonnet-5
Tokens: 1500 in / 271 out
Latency: 6937 ms
Called: 2026-08-09 07:01:09

Flag explanation

Mechanical clause 7 is a mutual coordination note that directly corresponds to fire_protection clause 7 (both reference the SP-14/D-6 note), and both point to the underlying physical conflict identified in fire_protection clause 2: sprinkler head SP-14 and HVAC diffuser D-6 are shown occupying the same ceiling grid cell, which is a physically incompatible layout that must be resolved before ceiling grid installation.

Prompt sent to model

Clause '7' (mechanical):
7. Coordinate ceiling-mounted device locations with the fire protection engineer prior to ceiling grid installation; see the D-6 note above.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: 0728c639-1e8b-43bd-8ff5-4c53a58fbfef] fire_protection 7: 7. Coordinate all ceiling-mounted device locations with the mechanical engineer prior to ceiling grid installation; see the SP-14/D-6 note above.

[id: a0bcc415-b67f-4d57-9c70-93086c479f8c] electrical 7: 7. Coordinate emergency/egress lighting fixture locations with the life safety plan, A-102.

[id: eb4b271b-cd36-4ea4-b0f8-acd9a3567650] fire_protection 2: 2. Sprinkler head SP-14, serving Sterilization 110, is shown at the same ceiling grid cell as HVAC supply diffuser D-6 on the mechanical plan (M-101). Relocate one of these two devices prior to ceiling grid installation so that neither obstructs the other's required coverage
or spray pattern -- as currently shown, they occupy the same ceiling location.

[id: 1b57eceb-1772-49a5-9732-f29f00aaca1a] civil 9: 9. Coordinate the water service / duct bank crossing with the electrical engineer; see the site utilities note above.

[id: ff697613-9a6f-43c9-9d68-1c62622dcf2e] architectural 4: 4. See S-101 for column and structural grid locations.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "Mechanical clause 7 is a mutual coordination note that directly corresponds to fire_protection clause 7 (both reference the SP-14/D-6 note), and both point to the underlying physical conflict identified in fire_protection clause 2: sprinkler head SP-14 and HVAC diffuser D-6 are shown occupying the same ceiling grid cell, which is a physically incompatible layout that must be resolved before ceiling grid installation.", "cited_clause_ids": ["0728c639-1e8b-43bd-8ff5-4c53a58fbfef", "eb4b271b-cd36-4ea4-b0f8-acd9a3567650"]}]}