Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 2
Severity: high
Engine: real / claude-sonnet-5
Tokens: 1662 in / 353 out
Latency: 4398 ms
Called: 2026-08-15 19:08:48

Flag explanation

The project clause provides only 30 inches of clear working space in front of Panel EP-2, but local amendment clause 3 requires a six foot (72 inch / 1829 mm) clear working space in front of all panels. 30 inches fails to meet this jurisdiction-specific minimum by a wide margin (and even the panel's own stated 36-inch NEC-based minimum falls short of the local 72-inch requirement).

Prompt sent to model

Project clause '2':
2. Panel EP-2 (Mech/Elec Room 105, 120/208V, 30-circuit) is shown with 30" of dedicated clear working space in front of it. The minimum clear working space required for a panel at this voltage-to-ground condition is 36"; the 30" shown does not meet that minimum on its
own, before even accounting for other equipment in the room.

Candidate jurisdiction code clauses (local amendments - only these may be cited):
[id: 34bcc862-3380-4533-a201-e83bf630d987] 3: 3.   A six foot (1829 mm) clear working space shall be provided in front of all panels.

[id: ee312677-be70-48d7-8c59-392bc8c6bbf6] 1204.2.2: 1204.2.2 Adjoining spaces.
For the purpose of natural lighting, any room is permitted to be considered as a portion of an adjoining room 
one-half of the area of the common wall is open and unobstructed and provides an opening of not less than 10
floor area of the interior room or 25 square feet (2.32 m2), whichever is greater. The net glazed area of exteri

[id: fca99166-362b-472d-acb9-04bab145d7e3] 2: 2.   Panels shall not be located in a separate room.

[id: 2ce77581-41ff-4233-b119-54420ca5a1e0] 10: 10.   Add a new Section 1006.2.2.7 to read:
"1006.2.2.7 Electrical rooms.
Two exit access doorways are required in electrical rooms containing equipment rated 3,000 amperes or greater. Exit
doorways shall be separated by a horizontal distance equal to not less than one-half the length of the maximum overa
dimension of the room."

[id: 0f9fe4e2-6c5a-46cd-8f22-dbe07b0c09a6] Section 1202.5: Section 1202.5 shall be provided in all living, dining and sleeping rooms with a floor area of 7
(6.5 m 2 ) or more.

These candidates are local amendments to the national model building code (e.g. IBC), not the full code. You may draw on your own general knowledge of standard model-code provisions to judge whether the project clause is consistent with normal practice, but any conflict you report must be grounded in - and cite - one of the local amendment clauses shown above, since those are the only things a human reviewer can independently verify against this jurisdiction's actual adopted text.

Does the project clause conflict with or fail to meet any of these code requirements? Call report_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "The project clause provides only 30 inches of clear working space in front of Panel EP-2, but local amendment clause 3 requires a six foot (72 inch / 1829 mm) clear working space in front of all panels. 30 inches fails to meet this jurisdiction-specific minimum by a wide margin (and even the panel's own stated 36-inch NEC-based minimum falls short of the local 72-inch requirement).", "cited_jurisdiction_clause_ids": ["34bcc862-3380-4533-a201-e83bf630d987"]}, {"severity": "high", "explanation": "Panel EP-2 is located in a dedicated Mech/Elec Room (Room 105), which conflicts with local amendment clause 2 stating that panels shall not be located in a separate room.", "cited_jurisdiction_clause_ids": ["fca99166-362b-472d-acb9-04bab145d7e3"]}]}