Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 6
Severity: high
Engine: real / claude-sonnet-5
Tokens: 1689 in / 243 out
Latency: 3854 ms
Called: 2026-08-09 07:01:09

Flag explanation

BM-7 is structurally designed for a 2,000 lb concentrated point load, but the mechanical engineer's selected RTU-1 has a stated operating weight of 3,200 lb including curb and rigging, exceeding the beam's design capacity by 1,200 lb. The beam must be resized before RTU-1 is set, per both the structural and mechanical notes.

Prompt sent to model

Clause '6' (structural):
6. BM-7's 2,000 lb design point load is intended to cover the rooftop unit anticipated for this tenant space. Confirm the actual operating weight of the rooftop unit selected by the mechanical engineer (see M-101) does not exceed this 2,000 lb design allowance; if it does,
this beam will need to be resized before the unit is set.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: d077053e-e241-45c1-92af-6d4ed9ea4fc4] mechanical 1: 1. RTU-1 is a 5-ton packaged rooftop unit located over Grid B3, with an operating weight of 3,200 lb including curb and rigging. This weight should be checked against the structural engineer's roof beam design at this location (see S-101, beam BM-7) before the unit is
ordered or set -- BM-7 is currently designed for a 2,000 lb concentrated point load at this location, which is less than RTU-1's stated operating weight.

[id: 8134ea51-ab17-4add-9fb1-ab1dcdc9c893] mechanical 5: 5. Verify roof structure capacity with the structural engineer prior to setting any rooftop equipment; see the RTU-1 note above.

[id: 5c4f36b0-8c7e-4e0a-875f-61ada1072b00] fire_protection 6: 6. Confirm occupant load basis with the architect before finalizing exit signage counts; see the note above.

[id: ef0c7a2e-015d-4659-9824-fb2b7131ef99] fire_protection 5: 5. Note: the architectural life safety plan (A-102) calculates the occupant load for this same floor as 85 persons, based on the final room program. Compare that figure against the 60-person design basis used here -- if 85 is correct, the exit signage count and hydraulic
calculation on this sheet should be revised accordingly.

[id: 0728c639-1e8b-43bd-8ff5-4c53a58fbfef] fire_protection 7: 7. Coordinate all ceiling-mounted device locations with the mechanical engineer prior to ceiling grid installation; see the SP-14/D-6 note above.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "BM-7 is structurally designed for a 2,000 lb concentrated point load, but the mechanical engineer's selected RTU-1 has a stated operating weight of 3,200 lb including curb and rigging, exceeding the beam's design capacity by 1,200 lb. The beam must be resized before RTU-1 is set, per both the structural and mechanical notes.", "cited_clause_ids": ["d077053e-e241-45c1-92af-6d4ed9ea4fc4", "8134ea51-ab17-4add-9fb1-ab1dcdc9c893"]}]}