Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 1.1
Severity: high
Engine: groq / llama-3.3-70b-versatile
Tokens: 916 in / 96 out
Latency: 548 ms
Called: 2026-07-22 04:49:53

Flag explanation

The mechanical clause requires a minimum clearance of 9 feet 6 inches, while the structural clause provides a minimum clear height of 9 feet 0 inches within the same corridor, Corridor 104, creating a physically incompatible condition.

Prompt sent to model

Clause '1.1' (mechanical):
1.1 Ductwork DS-2 within Corridor 104 shall maintain a minimum clearance of 9 feet 6 inches above finished floor to the bottom of duct insulation.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: 42249cff-18ae-4182-9bc0-7eb5c43a096f] structural 1.1: 1.1 Structural beam B-4 provides a minimum clear height of 9 feet 0 inches above finished floor within Corridor 104.

[id: fffc650d-fe44-43f6-b2b0-7c864393b9e8] structural 1.2: 1.2 Structural beam B-7 provides a minimum clear height of 8 feet 6 inches above finished floor within Corridor 109.

[id: 3c277c45-28b0-4b89-a46f-45a3b21cb96c] electrical 1.1: 1.1 Panel EP-3 in Electrical Room 118 requires a 36 inch clear working space per NEC in front of the panel, mounted on the north wall.

[id: 81c2bca1-6531-44ce-a8a7-91d776c5527c] electrical 1.2: 1.2 Panel EP-6 in Electrical Room 121 requires a 36 inch clear working space per NEC in front of the panel, mounted on the south wall.

[id: 47423ac6-f6a1-4630-bd8e-16b379b58056] architectural 1.2: 1.2 Door D-15 swings outward into the corridor, away from Electrical Room 121.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"cited_clause_ids": ["42249cff-18ae-4182-9bc0-7eb5c43a096f"], "explanation": "The mechanical clause requires a minimum clearance of 9 feet 6 inches, while the structural clause provides a minimum clear height of 9 feet 0 inches within the same corridor, Corridor 104, creating a physically incompatible condition.", "severity": "high"}]}