Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 6
Severity: medium
Engine: real / claude-sonnet-5
Tokens: 1551 in / 373 out
Latency: 4759 ms
Called: 2026-08-09 07:01:09

Flag explanation

Plumbing clause 8 calls for verifying WH-1's clearance from the east wall against the electrical panel clearance shown on E-101, directly referencing the same working clearance requirement mandated in electrical clause 6, indicating an unresolved coordination issue between the water heater placement and the panel's required dedicated space.

Prompt sent to model

Clause '6' (electrical):
6. Dedicated equipment space and working clearance for all panels shall meet the applicable electrical code requirements for the voltage and condition shown; see the EP-1 and EP-2 notes above.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: fd258c05-ae45-486c-b520-aaadb73a7a29] plumbing 2: 2. Coordinate WH-1's location with the electrical engineer's Panel EP-2, shown on E-101 on the same wall -- EP-2 requires 36" of dedicated clear working space, and WH-1 as located reduces the usable clear floor space in front of that panel to approximately 18".

[id: 8892de18-a105-4ab1-bfae-ec307cfbae22] plumbing 8: 8. Verify WH-1 clearance from the east wall against the electrical panel clearance requirements shown on E-101 before setting the unit; see the WH-1 notes above.

[id: 0728c639-1e8b-43bd-8ff5-4c53a58fbfef] fire_protection 7: 7. Coordinate all ceiling-mounted device locations with the mechanical engineer prior to ceiling grid installation; see the SP-14/D-6 note above.

[id: 79dd5322-efb5-4bae-93e6-d64eae7dff40] architectural 5: 5. Corridor 106 clear width shown 3'-4" (40") -- VERIFY code
   minimum for occupant load served (see A-102 egress calc).

[id: 126c3988-6be8-4b6d-ab91-5f3019c095f8] mechanical 7: 7. Coordinate ceiling-mounted device locations with the fire protection engineer prior to ceiling grid installation; see the D-6 note above.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "Electrical clause 6 requires panel working clearance (per EP-1/EP-2 notes) to meet code minimums (typically 36\" for the voltage/condition shown). Plumbing clause 2 states WH-1's location reduces the clear working space in front of Panel EP-2 to approximately 18\", which is physically incompatible with the required dedicated working clearance.", "cited_clause_ids": ["fd258c05-ae45-486c-b520-aaadb73a7a29"]}, {"severity": "medium", "explanation": "Plumbing clause 8 calls for verifying WH-1's clearance from the east wall against the electrical panel clearance shown on E-101, directly referencing the same working clearance requirement mandated in electrical clause 6, indicating an unresolved coordination issue between the water heater placement and the panel's required dedicated space.", "cited_clause_ids": ["8892de18-a105-4ab1-bfae-ec307cfbae22"]}]}