Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 2
Severity: high
Engine: real / claude-sonnet-5
Tokens: 1784 in / 225 out
Latency: 3524 ms
Called: 2026-08-15 19:08:47

Flag explanation

The jurisdiction's local amendment requires a six-foot (72") clear working space in front of all electrical panels. The project clause states that WH-1's location reduces the clear floor space in front of Panel EP-2 to approximately 18", far short of the 36" the electrical engineer requested and drastically short of the 72" mandated by the local amendment. This is a direct conflict with the code requirement.

Prompt sent to model

Project clause '2':
2. Coordinate WH-1's location with the electrical engineer's Panel EP-2, shown on E-101 on the same wall -- EP-2 requires 36" of dedicated clear working space, and WH-1 as located reduces the usable clear floor space in front of that panel to approximately 18".

Candidate jurisdiction code clauses (local amendments - only these may be cited):
[id: 34bcc862-3380-4533-a201-e83bf630d987] 3: 3.   A six foot (1829 mm) clear working space shall be provided in front of all panels.

[id: ee312677-be70-48d7-8c59-392bc8c6bbf6] 1204.2.2: 1204.2.2 Adjoining spaces.
For the purpose of natural lighting, any room is permitted to be considered as a portion of an adjoining room 
one-half of the area of the common wall is open and unobstructed and provides an opening of not less than 10
floor area of the interior room or 25 square feet (2.32 m2), whichever is greater. The net glazed area of exteri

[id: 2ce77581-41ff-4233-b119-54420ca5a1e0] 10: 10.   Add a new Section 1006.2.2.7 to read:
"1006.2.2.7 Electrical rooms.
Two exit access doorways are required in electrical rooms containing equipment rated 3,000 amperes or greater. Exit
doorways shall be separated by a horizontal distance equal to not less than one-half the length of the maximum overa
dimension of the room."

[id: 393cb432-34db-4166-9110-2b395f096341] 1031.2: 1031.2 Fire department access panels.
Where the exterior wall on any story of a Group E-1 occupancy exceeds 100 linear feet (30.5 m) without windows, d
similar openings, fire department access panels shall be provided at intervals not exceeding 50 feet (15.2 m).
Exception: Exterior walls of auditoriums, assembly halls, field houses, gymnasiums, swimming pools, and t

[id: f685e9bb-d88a-4e08-a6f0-9ab5d69bf015] 2: 2.   Revise items 1 and 2 in Section 419.1.1 to read:
"1.   The live/work unit shall be not less than 800 square feet (74.3 m2) and not greater than 3,000 square feet (279 m2
area.

These candidates are local amendments to the national model building code (e.g. IBC), not the full code. You may draw on your own general knowledge of standard model-code provisions to judge whether the project clause is consistent with normal practice, but any conflict you report must be grounded in - and cite - one of the local amendment clauses shown above, since those are the only things a human reviewer can independently verify against this jurisdiction's actual adopted text.

Does the project clause conflict with or fail to meet any of these code requirements? Call report_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "The jurisdiction's local amendment requires a six-foot (72\") clear working space in front of all electrical panels. The project clause states that WH-1's location reduces the clear floor space in front of Panel EP-2 to approximately 18\", far short of the 36\" the electrical engineer requested and drastically short of the 72\" mandated by the local amendment. This is a direct conflict with the code requirement.", "cited_jurisdiction_clause_ids": ["34bcc862-3380-4533-a201-e83bf630d987"]}]}