Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 1
Severity: high
Engine: real / claude-sonnet-5
Tokens: 1660 in / 418 out
Latency: 6844 ms
Called: 2026-08-09 07:01:09

Flag explanation

RTU-1's stated operating weight of 3,200 lb exceeds the 2,000 lb concentrated point load capacity that BM-7 was designed for at Grid B3. Both the mechanical clause and structural clauses 6 and 4 reference the same beam (BM-7) and location (Grid B3), and the mechanical unit's actual weight surpasses the structural design allowance, requiring the beam to be resized before the unit is set.

Prompt sent to model

Clause '1' (mechanical):
1. RTU-1 is a 5-ton packaged rooftop unit located over Grid B3, with an operating weight of 3,200 lb including curb and rigging. This weight should be checked against the structural engineer's roof beam design at this location (see S-101, beam BM-7) before the unit is
ordered or set -- BM-7 is currently designed for a 2,000 lb concentrated point load at this location, which is less than RTU-1's stated operating weight.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: 24c657a2-1519-4127-916a-b5087bb79878] structural 6: 6. BM-7's 2,000 lb design point load is intended to cover the rooftop unit anticipated for this tenant space. Confirm the actual operating weight of the rooftop unit selected by the mechanical engineer (see M-101) does not exceed this 2,000 lb design allowance; if it does,
this beam will need to be resized before the unit is set.

[id: acbf29dd-bce3-4730-8058-60eac610cb57] structural 4: 4. Beam BM-7 (roof, over Grid B3): W14X30, 20'-0" long, designed for a concentrated point load of 2,000 lb at midspan to accommodate future rooftop mechanical equipment.

[id: 570c9fd7-f475-47eb-a09d-2874b6c08d9c] structural 8: 8. Existing roof structure to remain except as noted; new point loads from mechanical equipment require verification against the original roof design documents, which are not available for this building -- the 2,000 lb allowance noted above for BM-7 is an assumed allowable
pending that verification.

[id: ef1a85ae-92bf-4a9c-b039-84a876adae63] structural 2: 2. Beam BM-1 (Grid B, bay 1-2): W10X22, 24'-0" long, bottom of steel +9'-0" AFF.

[id: ff697613-9a6f-43c9-9d68-1c62622dcf2e] architectural 4: 4. See S-101 for column and structural grid locations.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "RTU-1's stated operating weight of 3,200 lb exceeds the 2,000 lb concentrated point load capacity that BM-7 was designed for at Grid B3. Both the mechanical clause and structural clauses 6 and 4 reference the same beam (BM-7) and location (Grid B3), and the mechanical unit's actual weight surpasses the structural design allowance, requiring the beam to be resized before the unit is set.", "cited_clause_ids": ["24c657a2-1519-4127-916a-b5087bb79878", "acbf29dd-bce3-4730-8058-60eac610cb57"]}, {"severity": "medium", "explanation": "The structural note indicates the 2,000 lb allowance for BM-7 is only an assumed value pending verification against unavailable original roof design documents, adding further uncertainty to whether BM-7 can support RTU-1's 3,200 lb operating weight, compounding the incompatibility identified with the beam's design load.", "cited_clause_ids": ["570c9fd7-f475-47eb-a09d-2874b6c08d9c"]}]}