The project clause proposes a 40-inch (3'-4") clear width for Corridor 106 serving an 85-person occupant load, but the jurisdiction's amended Table 1020.2 (Minimum Corridor Width) establishes the controlling minimum width requirements based on occupant load. Standard model code minimum corridor width for occupant loads of 50 or more is typically 44 inches, which would exceed the 40-inch width shown on A-101. Since Table 1020.2 has been locally replaced, the 40-inch dimension must be verified against this specific table before construction proceeds, as it likely fails to meet the required minimum for an 85-person load.
Prompt sent to model
Project clause '4':
4. Corridor 106 is dimensioned at 3'-4" (40") clear width on A-101; confirm this width against the minimum corridor width required for an 85-person occupant load before construction proceeds, since this corridor is the sole path of travel for the rear two-thirds of the tenant
space.
Candidate jurisdiction code clauses (local amendments - only these may be cited):
[id: cb54b783-ceca-43fd-82e4-46c9e967dfd2] 5: 5. Corridors, at intervals not exceeding 75 feet (22.9 m).
[id: 633ccaef-f0d5-4857-b429-14e6342e1959] 14: 14. Revise Section 1010.1.6 to read:
"1010.1.6 Landings at doors.
Landings shall have a width not less than the width of the stairway or the door, whichever is greater. Doors in the ful
position shall not reduce a required dimension by more than one-quarter its required width. Landings shall have a len
in the direction of travel of not less than 44 inches (1118 mm).
Exception: Landing length in the direction of travel in Groups R-3, R-5 and U and within individual units of
need not exceed 36 inches (914 mm)."
[id: 65f9554c-5a9b-4700-8ba7-e173c6c9af1e] 203.5.2: 203.5.2 Net floor area.
Net floor area shall be the actual occupiable horizontal area, not including columns, permanently attached eq
furnishings that are 28 inches (711 mm) or greater above the floor, the thickness of interior walls and unoccu
areas such as aisles, corridors, stairways, ramps, individual wellness/lactation rooms, toilet rooms, mechanic
closets."
(Amend Coun. J. 7-24-19, p. 3646, § 25; Amend Coun. J. 2-19-20, p. 14473, Art. II, § 2; Amend Coun. J. 6-25-21, p. 32180,
Amend Coun. J. 1-26-22, p. 43756, Art. II, § 2)
CHAPTER 14B-3
OCCUPANCY CLASSIFICATION AND USE
[id: ac6f1abf-9913-4615-9afd-b92770f88a6c] 3: 3. Replace Table 1020.2 as shown:
TABLE 1020.2
MINIMUM CORRIDOR WIDTH
[id: c624fe51-5d5f-4fe2-94b8-c32ccd94e2d3] 2: 2. Revise Section 1007.1.1 to read:
"1007.1.1 Two exits or exit access doorways.
Where two exits, exit access doorways, exit access stairways or exit access ramps, or any combination thereof, are re
any portion of the exit access, they shall be placed a distance apart equal to not less than one- half of the length of th
overall diagonal dimension of the building or area to be served measured in a straight line between them.
Exceptions:
These candidates are local amendments to the national model building code (e.g. IBC), not the full code. You may draw on your own general knowledge of standard model-code provisions to judge whether the project clause is consistent with normal practice, but any conflict you report must be grounded in - and cite - one of the local amendment clauses shown above, since those are the only things a human reviewer can independently verify against this jurisdiction's actual adopted text.
Does the project clause conflict with or fail to meet any of these code requirements? Call report_conflicts with your findings, or an empty conflicts list if there's no real conflict.
Raw model response
{"conflicts": [{"severity": "medium", "explanation": "The project clause proposes a 40-inch (3'-4\") clear width for Corridor 106 serving an 85-person occupant load, but the jurisdiction's amended Table 1020.2 (Minimum Corridor Width) establishes the controlling minimum width requirements based on occupant load. Standard model code minimum corridor width for occupant loads of 50 or more is typically 44 inches, which would exceed the 40-inch width shown on A-101. Since Table 1020.2 has been locally replaced, the 40-inch dimension must be verified against this specific table before construction proceeds, as it likely fails to meet the required minimum for an 85-person load.", "cited_jurisdiction_clause_ids": ["ac6f1abf-9913-4615-9afd-b92770f88a6c"]}]}