Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 1.2
Severity: medium
Engine: groq / llama-3.3-70b-versatile
Tokens: 928 in / 89 out
Latency: 581 ms
Called: 2026-07-22 04:21:30

Flag explanation

The door swing into the corridor may conflict with the required 36 inch deep working clearance for Switchgear SG-4 in Electrical Room 214, as the door may encroach into this clearance zone.

Prompt sent to model

Clause '1.2' (architectural):
1.2 Door D-24 to Electrical Room 214 swings outward into the corridor, clear of the room's interior wall faces.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: 23ed8451-9f6f-4fdc-8da7-e294767c7174] electrical 1.2: 1.2 Switchgear SG-4 in Electrical Room 214 requires a dedicated 36 inch deep working clearance, free of any other trade's infrastructure, per NEC 110.26.

[id: b88a0614-b3f5-45b1-ab48-78fc7d2547c1] electrical 1.1: 1.1 Switchgear SG-2 in Electrical Room 210 requires a dedicated 42 inch deep working clearance, free of any other trade's infrastructure, per NEC 110.26.

[id: 1f2af6ee-21b9-49c9-88d6-58730760c2e8] electrical 1.2: 1.2 Cable tray CT-8 is routed through Electrical Room 214 along the ceiling, outside the switchgear SG-4 working clearance zone.

[id: 47f5d696-206b-4fb1-be22-5cdb1ff00e4b] low_voltage 1.2: 1.2 Structured cabling tray for the BMS backbone runs through Electrical Room 214 at ceiling height, outside the switchgear SG-4 working clearance zone.

[id: 1e846493-c72d-463a-ab51-3490c8882962] electrical 2.1: 2.1 Panel EP-9 in Data Hall 1 electrical closet is wall-mounted at 5 feet 0 inches above finished floor.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"cited_clause_ids": ["23ed8451-9f6f-4fdc-8da7-e294767c7174"], "explanation": "The door swing into the corridor may conflict with the required 36 inch deep working clearance for Switchgear SG-4 in Electrical Room 214, as the door may encroach into this clearance zone.", "severity": "medium"}]}