Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 1.1
Severity: high
Engine: groq / llama-3.3-70b-versatile
Tokens: 939 in / 171 out
Latency: 3590 ms
Called: 2026-07-22 04:23:03

Flag explanation

The structural beam B-14 provides a minimum clear height of 14 feet 0 inches above finished floor within Data Hall 2, which is below the required duct insulation clearance of 14 feet 6 inches.

Prompt sent to model

Clause '1.1' (mechanical):
1.1 Ductwork DS-11 within Data Hall 2 shall maintain a minimum clearance of 14 feet 6 inches above finished floor to the bottom of duct insulation.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: f293f8e9-335d-46ec-9bd6-fbdeb528c2db] architectural 1.2: 1.2 Reflected ceiling plan for Data Hall 4 requires a minimum 8 feet 6 inches clear from finished floor to the underside of any overhead equipment, duct, tray, or pipe.

[id: 31c0c6f8-2ce0-4848-a79c-a4ed1534ec37] architectural 1.1: 1.1 Reflected ceiling plan for Data Hall 1 requires a minimum 9 feet 0 inches clear from finished floor to the underside of any overhead equipment, duct, tray, or pipe.

[id: b3006913-bda3-46fb-a810-1b8012937fea] fire_protection 1.1: 1.1 Sprinkler branch line SP-6 crosses Data Hall 2 at 14 feet 3 inches above finished floor, below the required duct insulation clearance.

[id: 6df910bd-5ca1-47fc-b6a3-2cc753e73bc4] structural 1.1: 1.1 Structural beam B-14 provides a minimum clear height of 14 feet 0 inches above finished floor within Data Hall 2.

[id: 57d266d8-7540-4012-a959-7ebd1ec2a38c] structural 1.2: 1.2 Structural beam B-19 provides a minimum clear height of 15 feet 0 inches above finished floor within Data Hall 3.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"cited_clause_ids": ["b3006913-bda3-46fb-a810-1b8012937fea"], "explanation": "The sprinkler branch line SP-6 crosses Data Hall 2 at 14 feet 3 inches above finished floor, which is below the required duct insulation clearance of 14 feet 6 inches.", "severity": "high"}, {"cited_clause_ids": ["6df910bd-5ca1-47fc-b6a3-2cc753e73bc4"], "explanation": "The structural beam B-14 provides a minimum clear height of 14 feet 0 inches above finished floor within Data Hall 2, which is below the required duct insulation clearance of 14 feet 6 inches.", "severity": "high"}]}