Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 1
Severity: low
Engine: real / claude-sonnet-5
Tokens: 1615 in / 425 out
Latency: 6667 ms
Called: 2026-08-09 07:01:09

Flag explanation

Architectural clause 4 directs reliance on S-101 for column and grid locations, which is the same structural document containing the 48'-0" dimension that conflicts with the field-verified 47'-6" dimension shown elsewhere on architectural drawings; this reinforces the need for coordination but is not itself a new conflict.

Prompt sent to model

Clause '1' (structural):
1. All new and existing columns are located strictly on the structural grid unless individually dimensioned otherwise. The column at Grid C/3, adjacent to the Sterilization/Storage partition, is located on grid at 48'-0" from Grid 1. The architectural floor plan (A-101)
dimensions this same column at 47'-6" from Grid 1 based on field conditions observed during their site walkthrough. Reconcile this 6" discrepancy with the architect before partitions or casework are set relative to this column.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: ff697613-9a6f-43c9-9d68-1c62622dcf2e] architectural 4: 4. See S-101 for column and structural grid locations.

[id: 2452871c-f8e5-4c3c-aaf8-8450d0c26eec] architectural 6: 6. Column at Grid C/3 dimensioned 47'-6" from Grid 1 per
   existing field conditions -- coordinate with S-101 which
   shows column on grid (48'-0").

[id: c73a7928-adc3-4923-9be6-b56d6747c661] architectural 4: 4. Corridor 106 is dimensioned at 3'-4" (40") clear width on A-101; confirm this width against the minimum corridor width required for an 85-person occupant load before construction proceeds, since this corridor is the sole path of travel for the rear two-thirds of the tenant
space.

[id: 0728c639-1e8b-43bd-8ff5-4c53a58fbfef] fire_protection 7: 7. Coordinate all ceiling-mounted device locations with the mechanical engineer prior to ceiling grid installation; see the SP-14/D-6 note above.

[id: 4b689f5a-537b-4d68-9d7d-399f2536095c] architectural 113: 113
COL
DIM'D @ 47'-6" FROMIGRID 1 (FIELD VERIFY)

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "Structural clause locates the column at Grid C/3 at 48'-0\" from Grid 1 (on grid), while architectural drawing A-101 dimensions the same column at 47'-6\" from Grid 1 based on field-verified conditions. This 6\" discrepancy in column location directly affects placement of the adjacent Sterilization/Storage partition and casework, and must be reconciled between structural and architectural before those elements are set.", "cited_clause_ids": ["2452871c-f8e5-4c3c-aaf8-8450d0c26eec", "4b689f5a-537b-4d68-9d7d-399f2536095c"]}, {"severity": "low", "explanation": "Architectural clause 4 directs reliance on S-101 for column and grid locations, which is the same structural document containing the 48'-0\" dimension that conflicts with the field-verified 47'-6\" dimension shown elsewhere on architectural drawings; this reinforces the need for coordination but is not itself a new conflict.", "cited_clause_ids": ["ff697613-9a6f-43c9-9d68-1c62622dcf2e"]}]}