Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 6
Severity: high
Engine: real / claude-sonnet-5
Tokens: 1762 in / 328 out
Latency: 4255 ms
Called: 2026-08-15 19:08:47

Flag explanation

The project clause specifies an exit stair handrail height of 30" AFF measured vertically from the leading edge of the treads. Local amendments 5b625195-d0ea-4e0f-9073-f49c50580dfc and 6cf5148e-30d8-4931-bdc7-16fed0101474 require handrails/guards on open sides of stairs (including where a guard serves as a handrail) to be not less than 34 inches and not more than 38 inches measured vertically from a line connecting the leading edges of the treads. The noted 30" height falls below this required minimum of 34", conflicting with the applicable code range.

Prompt sent to model

Project clause '6':
6. Exit stair handrail (Detail A-102.1): the exit stair handrail at the rear egress stair is noted at a height of 30" AFF, measured vertically from the leading edge of the stair treads. Confirm this height against the applicable handrail/guard height range for stairs before
installation; the height as noted appears low relative to the typical 34"-38" range used elsewhere in similar occupancies.

Candidate jurisdiction code clauses (local amendments - only these may be cited):
[id: 12398a8a-b942-4aaf-9bdc-0ca21748bcbf] 2: 2.   Revise Section 1027.5 to read:
"1027.5 Location.
Exterior exit stairways and exterior exit ramps shall have a minimum separation distance of 10 feet (3048 mm) meas
angles from the exterior edge of the stairway or ramps, including landings, to:

[id: 5b625195-d0ea-4e0f-9073-f49c50580dfc] 3: 3.   For occupancies in Group R-3 and R-5, and within individual dwelling units in occupancies in Group R-2
of the guard serves as a handrail on the open sides of stairs, the top of the guard shall be not less than 34 inc
and not more than 38 inches (965 mm) measured vertically from a line connecting the leading edges of the tr

[id: 708b6180-fee1-42c5-a03f-5bae8c73b887] 11: 11.   Revise Section 1011.8 to read:
"1011.8 Vertical rise.
A flight of stairs shall not have a vertical rise greater than 12 feet (3658 mm) between floor levels or landings.
Exceptions:

[id: e16aebfb-0ac7-4aa8-ba37-f93d6416b3d3] 11: 11 where the risers and treads comply with Section 1011.5, the minimum depth of the tread is 13 inches (330
handrail is provided in accordance with Section 1014."

[id: 6cf5148e-30d8-4931-bdc7-16fed0101474] 2: 2.   For occupancies in Group R-3 and R-5, and within individual dwelling units in occupancies in Group R-2
open sides of stairs shall have a height not less than 34 inches (864 mm) measured vertically from a line conn
leading edges of the treads.

These candidates are local amendments to the national model building code (e.g. IBC), not the full code. You may draw on your own general knowledge of standard model-code provisions to judge whether the project clause is consistent with normal practice, but any conflict you report must be grounded in - and cite - one of the local amendment clauses shown above, since those are the only things a human reviewer can independently verify against this jurisdiction's actual adopted text.

Does the project clause conflict with or fail to meet any of these code requirements? Call report_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "The project clause specifies an exit stair handrail height of 30\" AFF measured vertically from the leading edge of the treads. Local amendments 5b625195-d0ea-4e0f-9073-f49c50580dfc and 6cf5148e-30d8-4931-bdc7-16fed0101474 require handrails/guards on open sides of stairs (including where a guard serves as a handrail) to be not less than 34 inches and not more than 38 inches measured vertically from a line connecting the leading edges of the treads. The noted 30\" height falls below this required minimum of 34\", conflicting with the applicable code range.", "cited_jurisdiction_clause_ids": ["5b625195-d0ea-4e0f-9073-f49c50580dfc", "6cf5148e-30d8-4931-bdc7-16fed0101474"]}]}