Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 1.1
Severity: high
Engine: real / claude-sonnet-5
Tokens: 1488 in / 208 out
Latency: 4652 ms
Called: 2026-08-15 19:04:35

Flag explanation

Panel EP-3 requires a 36 inch clear working space in front of it mounted on the north wall of Electrical Room 118. Door D-12 swings into the same room with a 36 inch swing radius centered 6 inches off the north wall, meaning the door swing will encroach into the required NEC clear working space in front of the panel, creating a physical/functional conflict.

Prompt sent to model

Clause '1.1' (electrical):
1.1 Panel EP-3 in Electrical Room 118 requires a 36 inch clear working space per NEC in front of the panel, mounted on the north wall.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: f480374a-5e74-4e06-a424-f19f96f8c542] architectural 1.1: 1.1 Door D-12 swings into Electrical Room 118 with a 36 inch swing radius centered 6 inches off the north wall.

[id: 47423ac6-f6a1-4630-bd8e-16b379b58056] architectural 1.2: 1.2 Door D-15 swings outward into the corridor, away from Electrical Room 121.

[id: 3d7a16c7-f33d-4cf7-9289-3a98972fec63] mechanical 1.1: 1.1 Ductwork DS-2 within Corridor 104 shall maintain a minimum clearance of 9 feet 6 inches above finished floor to the bottom of duct insulation.

[id: b87d8892-c9b4-4675-bc7e-da83a0e78a55] mechanical 1.2: 1.2 Ductwork DS-4 within Corridor 109 shall maintain a minimum clearance of 8 feet 6 inches above finished floor to the bottom of duct insulation.

[id: 42249cff-18ae-4182-9bc0-7eb5c43a096f] structural 1.1: 1.1 Structural beam B-4 provides a minimum clear height of 9 feet 0 inches above finished floor within Corridor 104.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "Panel EP-3 requires a 36 inch clear working space in front of it mounted on the north wall of Electrical Room 118. Door D-12 swings into the same room with a 36 inch swing radius centered 6 inches off the north wall, meaning the door swing will encroach into the required NEC clear working space in front of the panel, creating a physical/functional conflict.", "cited_clause_ids": ["f480374a-5e74-4e06-a424-f19f96f8c542"]}]}