Plan Review Copilot
← back to flags
Audit trail

Reasoning trace

Clause: 2
Severity: high
Engine: real / claude-sonnet-5
Tokens: 1645 in / 237 out
Latency: 3370 ms
Called: 2026-08-09 07:01:09

Flag explanation

Sprinkler head SP-14 and HVAC supply diffuser D-6, both serving Sterilization 110, are shown occupying the same ceiling grid cell on FP-101 and M-101 respectively. This is a direct physical clash requiring one device to be relocated before ceiling grid installation so neither obstructs the other's coverage/spray pattern.

Prompt sent to model

Clause '2' (fire_protection):
2. Sprinkler head SP-14, serving Sterilization 110, is shown at the same ceiling grid cell as HVAC supply diffuser D-6 on the mechanical plan (M-101). Relocate one of these two devices prior to ceiling grid installation so that neither obstructs the other's required coverage
or spray pattern -- as currently shown, they occupy the same ceiling location.

Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: f52da2fb-8a96-4462-b241-a0426ee77041] mechanical 3: 3. Supply and return diffusers are provided in each operatory, the waiting area, and break room per typical layout. Diffuser D-6, serving Sterilization 110, is located at the same ceiling grid cell as sprinkler head SP-14 shown on the fire protection plan (FP-101). Coordinate
with the fire protection engineer to relocate one of these two devices before the ceiling grid is installed, so that neither obstructs the other's required coverage.

[id: 126c3988-6be8-4b6d-ab91-5f3019c095f8] mechanical 7: 7. Coordinate ceiling-mounted device locations with the fire protection engineer prior to ceiling grid installation; see the D-6 note above.

[id: ada4f233-90a1-47cb-a3a7-975a4474df54] civil 6: 6. These two utilities cross near Station 0+20, and no horizontal or vertical separation is called out at the crossing -- coordinate the required clearance between the water service and the duct bank with the electrical engineer and the local utility standards before trenching.

[id: a0bcc415-b67f-4d57-9c70-93086c479f8c] electrical 7: 7. Coordinate emergency/egress lighting fixture locations with the life safety plan, A-102.

[id: 1b57eceb-1772-49a5-9732-f29f00aaca1a] civil 9: 9. Coordinate the water service / duct bank crossing with the electrical engineer; see the site utilities note above.

Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.

Raw model response

{"conflicts": [{"severity": "high", "explanation": "Sprinkler head SP-14 and HVAC supply diffuser D-6, both serving Sterilization 110, are shown occupying the same ceiling grid cell on FP-101 and M-101 respectively. This is a direct physical clash requiring one device to be relocated before ceiling grid installation so neither obstructs the other's coverage/spray pattern.", "cited_clause_ids": ["f52da2fb-8a96-4462-b241-a0426ee77041", "126c3988-6be8-4b6d-ab91-5f3019c095f8"]}]}