The project clause states that working clearance for panels shall meet 'applicable electrical code requirements for the voltage and condition shown,' implying standard NEC clearances (which vary by voltage/condition, often less than 6 feet). However, the local amendment mandates a fixed six-foot clear working space in front of all panels regardless of voltage or condition, which is a stricter, non-variable requirement that the project clause does not explicitly guarantee.
Prompt sent to model
Project clause '6':
6. Dedicated equipment space and working clearance for all panels shall meet the applicable electrical code requirements for the voltage and condition shown; see the EP-1 and EP-2 notes above.
Candidate jurisdiction code clauses (local amendments - only these may be cited):
[id: 9afdad69-77bd-4e04-9d68-c5827518fe35] 10: 10. All panels shall be clearly labeled at the top to indicate the purpose or function, such as "detectio
communication," "elevators," or "generator."
[id: 34bcc862-3380-4533-a201-e83bf630d987] 3: 3. A six foot (1829 mm) clear working space shall be provided in front of all panels.
[id: fca99166-362b-472d-acb9-04bab145d7e3] 2: 2. Panels shall not be located in a separate room.
[id: 2f3bb93c-628a-429d-91a3-675e78717d1e] 2: 2. Spaces within dwelling units and sleeping units, other than Accessible units and Type A units, and
egress from a single unit shall comply with Section 1207."
[id: 0e9b1849-ac61-44f8-9d7e-ba2f108dc5f5] 4: 4. Panels shall be mounted vertically on a wall.
These candidates are local amendments to the national model building code (e.g. IBC), not the full code. You may draw on your own general knowledge of standard model-code provisions to judge whether the project clause is consistent with normal practice, but any conflict you report must be grounded in - and cite - one of the local amendment clauses shown above, since those are the only things a human reviewer can independently verify against this jurisdiction's actual adopted text.
Does the project clause conflict with or fail to meet any of these code requirements? Call report_conflicts with your findings, or an empty conflicts list if there's no real conflict.
Raw model response
{"conflicts": [{"severity": "medium", "explanation": "The project clause states that working clearance for panels shall meet 'applicable electrical code requirements for the voltage and condition shown,' implying standard NEC clearances (which vary by voltage/condition, often less than 6 feet). However, the local amendment mandates a fixed six-foot clear working space in front of all panels regardless of voltage or condition, which is a stricter, non-variable requirement that the project clause does not explicitly guarantee.", "cited_jurisdiction_clause_ids": ["34bcc862-3380-4533-a201-e83bf630d987"]}]}