The site utility trench along column line 18 is excavated to 3 feet 0 inches below finished grade, which is above the footing F-18 bearing at 5 feet 0 inches below finished grade, potentially causing a conflict with the structural footing.
Clause '1.2' (civil): 1.2 Site utility trench along column line 18 is excavated to 3 feet 0 inches below finished grade for the domestic water tie-in. Candidate clauses from other disciplines in the same submission (only these may be cited): [id: d66ba874-2f49-48ee-889d-0eb337194bc1] structural 1.2: 1.2 Footing F-18 at column line 18 bears at 5 feet 0 inches below finished grade. [id: 845b47cf-d162-4d03-a31b-360cb129dfa2] plumbing 1.1: 1.1 Domestic water main enters the building at the northeast corner, 4 feet 0 inches below finished grade. [id: 728adafa-ab1a-41aa-aa61-b5b4f42c9e79] structural 1.1: 1.1 Footing F-12 at column line 12 bears at 3 feet 6 inches below finished grade. [id: fe0d6025-82ff-47ec-be1e-3dcbe8677631] fire_protection 1.2: 1.2 Sprinkler branch line SP-9 crosses Data Hall 3 at 12 feet 6 inches above finished floor. [id: 82a8c853-5961-4ef8-bdaf-dc261acc5afc] plumbing 1.2: 1.2 Restroom group RR-2 drainage ties into the sanitary main at 3 feet 6 inches below finished floor. Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.
{"conflicts": [{"cited_clause_ids": ["d66ba874-2f49-48ee-889d-0eb337194bc1"], "explanation": "The site utility trench along column line 18 is excavated to 3 feet 0 inches below finished grade, which is above the footing F-18 bearing at 5 feet 0 inches below finished grade, potentially causing a conflict with the structural footing.", "severity": "medium"}]}