← back to flags
Audit trail
Reasoning trace
Flag explanation
Electrical clause references the Restroom door swinging into Corridor 106 as room 104, conflicting with the panel EP-1 clearance zone. Since architectural clause 103 is the Accessible Restroom (possibly the same room referred to as 104 elsewhere), the door numbering discrepancy (103 vs 104) must be reconciled before confirming whether the door swing conflict applies to this room.
Prompt sent to model
Clause '103' (architectural):
103
RESTROOMI(ACCESSIBLE)
Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: bda06321-6b66-41b1-b882-36a2a9d03136] plumbing 4: 4. Restroom 104 (accessible) contains one water closet (3" waste / 2" vent) and one wall-hung lavatory (1-1/2" waste), both ADA compliant.
[id: c0db094c-d519-4117-b158-f553fcd13b52] electrical 1: 1. Panel EP-1 (Waiting/Office area, 120/208V, 42-circuit) requires a dedicated equipment clearance in front of the panel. This clearance zone is shown landing at the same stretch of Corridor 106 where the Restroom door (104) is shown swinging into the corridor on A-101
-- coordinate with the architect, since the door swing as drawn overlaps the panel's required clear working space.
[id: ef0c7a2e-015d-4659-9824-fb2b7131ef99] fire_protection 5: 5. Note: the architectural life safety plan (A-102) calculates the occupant load for this same floor as 85 persons, based on the final room program. Compare that figure against the 60-person design basis used here -- if 85 is correct, the exit signage count and hydraulic
calculation on this sheet should be revised accordingly.
[id: a0bcc415-b67f-4d57-9c70-93086c479f8c] electrical 7: 7. Coordinate emergency/egress lighting fixture locations with the life safety plan, A-102.
[id: b423d502-3196-4e58-83cd-43c48a4f5b68] plumbing 6: 6. Each of the four operatories (107, 108, 109, 112) has one clinical hand-wash sink (1-1/2" waste).
Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.
Raw model response
{"conflicts": [{"severity": "medium", "explanation": "Architectural room 103 is labeled as the Accessible Restroom, but the plumbing clause identifies the accessible restroom with matching ADA fixtures as room 104, not 103. This room numbering mismatch between architectural and plumbing drawings needs to be resolved to confirm the fixtures documented actually correspond to this room.", "cited_clause_ids": ["bda06321-6b66-41b1-b882-36a2a9d03136"]}, {"severity": "medium", "explanation": "Electrical clause references the Restroom door swinging into Corridor 106 as room 104, conflicting with the panel EP-1 clearance zone. Since architectural clause 103 is the Accessible Restroom (possibly the same room referred to as 104 elsewhere), the door numbering discrepancy (103 vs 104) must be reconciled before confirming whether the door swing conflict applies to this room.", "cited_clause_ids": ["c0db094c-d519-4117-b158-f553fcd13b52"]}]}