← back to flags
Audit trail
Reasoning trace
Flag explanation
Architectural clause 4 directs reliance on S-101 for column/grid locations, but structural clause 947c21fa notes a 6" discrepancy between the structural grid location of the column at Grid C/3 (48'-0" from Grid 1) and the architectural dimension on A-101 (47'-6" from Grid 1). This is a direct conflict in the same physical element (column location) that must be reconciled before partitions/casework are set.
Prompt sent to model
Clause '4' (architectural):
4. See S-101 for column and structural grid locations.
Candidate clauses from other disciplines in the same submission (only these may be cited):
[id: 947c21fa-7f9c-496f-ac30-271f27246407] structural 1: 1. All new and existing columns are located strictly on the structural grid unless individually dimensioned otherwise. The column at Grid C/3, adjacent to the Sterilization/Storage partition, is located on grid at 48'-0" from Grid 1. The architectural floor plan (A-101)
dimensions this same column at 47'-6" from Grid 1 based on field conditions observed during their site walkthrough. Reconcile this 6" discrepancy with the architect before partitions or casework are set relative to this column.
[id: d85768ef-17e9-4812-b54e-d3cc4d7b2e7f] mechanical 6: 6. Coordinate all duct routing crossing structural beam lines with the structural engineer's bottom-of-steel elevations shown on S-101; see the RA-1 note above.
[id: 0728c639-1e8b-43bd-8ff5-4c53a58fbfef] fire_protection 7: 7. Coordinate all ceiling-mounted device locations with the mechanical engineer prior to ceiling grid installation; see the SP-14/D-6 note above.
[id: 7f90f154-e493-43c1-a813-58091925da17] structural 3: 3. Beam BM-4 (Grid B, bay 2-3): W10X22, 24'-0" long, bottom of steel +9'-0" AFF -- note that the framing plan callout for BM-4 elsewhere on this sheet reads W12X26; field-verify and confirm the correct size with this office before fabrication, as the two callouts for the same
mark do not agree.
[id: 8134ea51-ab17-4add-9fb1-ab1dcdc9c893] mechanical 5: 5. Verify roof structure capacity with the structural engineer prior to setting any rooftop equipment; see the RTU-1 note above.
Does this clause create a coordination conflict with any of the candidates above - i.e. do they describe the same physical space, element, or system in a way that is physically or functionally incompatible? Call report_cross_discipline_conflicts with your findings, or an empty conflicts list if there's no real conflict.
Raw model response
{"conflicts": [{"severity": "medium", "explanation": "Architectural clause 4 directs reliance on S-101 for column/grid locations, but structural clause 947c21fa notes a 6\" discrepancy between the structural grid location of the column at Grid C/3 (48'-0\" from Grid 1) and the architectural dimension on A-101 (47'-6\" from Grid 1). This is a direct conflict in the same physical element (column location) that must be reconciled before partitions/casework are set.", "cited_clause_ids": ["947c21fa-7f9c-496f-ac30-271f27246407"]}]}