| Label | Text | Page | Extraction method |
| 1 |
1.
The producing mills shall sell or provide the lumber directly to the ultimate
consumer or his contract builder for use in an approved structure; |
- |
pdf_text |
| 1 |
1.
The fire area exceeds 5,000 square feet (464.5m2) |
- |
pdf_text |
| 1 |
1.
On buildings of Types I and II construction, three stories or less in height, fire-
retardant-treated wood shall be permitted for balconies, porches, decks, and
exterior stairways not used as required exits. |
- |
pdf_text |
| 1 |
1.
Building Code
SBC-1-2010 |
- |
pdf_text |
| 1 |
1. Agricultural and horticultural greenhouses used primarily for growing. |
- |
pdf_text |
| 1 |
1.
Sizing criteria: For lumber sized in accordance with the AF&PA NDS-01
conventional spantables in this code shall be permitted to be used for establishin
span and spacing characteristics for all structural members. |
- |
pdf_text |
| 1 |
1. Clear floor space: Clear floor space for water closets shall comply with
ICC/ANSI A117.1-2003-604.3.1. Clear floor space shall be permitted to be
arranged to allow either a left-handed or right-handed approach. |
- |
pdf_text |
| 1 |
1. See Rhode Island Frost Depth values in Table 1608.1. and Figure 1608.1 |
- |
pdf_text |
| 1 |
1.
Fire command center. |
- |
pdf_text |
| 1 |
1. Throughout all Group E fire areas greater than 20,000 square feet (1115 m2)
in area. |
- |
pdf_text |
| 1 |
1. Multiplier factor for Width = |
- |
pdf_text |
| 1 |
1.
Low lighting levels |
- |
pdf_text |
| 1 |
1.
Detached one-and two-family dwellings and multiple single-family
dwellings (town houses) not more than three stories above grade plane in
height with a separate means of egress and their accessory structures shall
comply with the SBC-2-2007 The Rhode Island One and Two Family
Dwelling Code. |
- |
pdf_text |
| 1 |
1.
When the existing wall or wall covering is water-soaked or has deteriorated to the
point that the existing wall or wall covering is not acceptable as a base for
additional covering. |
- |
pdf_text |
| 1 |
1.
Where the roof slope exceeds 20 units vertical in 12 units horizontal (20:12),
special fastening details may be required by the manufacturer. |
- |
pdf_text |
| 1 |
1.
Classified in Occupancy Category I, in accordance with Section |
- |
pdf_text |
| 1.14.2.2 |
1.14.2.2 of ACI 530/ASCE 5/TMS 402 and Section 1.14.3, 1.14.4, 1.14.5, 1.14.6 or |
- |
pdf_text |
| 1.14.7 |
1.14.7 of ACI 530/ASCE 5/TMS 402 depending on the structure’s seismic design
category as determined in Section 1616.3. In addition, the following requirements shall
be met.
SBC-1 2010
- 26 |
- |
pdf_text |
| 10 |
10.
Movable furnishings
The Building Official shall have the authority to determine whether a proposed use is
deemed a nightclub or a restaurant (see also section 903.2.1.2).
SBC-1 2010
- 4 |
- |
pdf_text |
| 10 |
10.
Code Interpretations
SBC-10 |
- |
pdf_text |
| 101.1 |
101.1 Title
This regulation shall be known as SBC-1-2007, the Rhode Island State Building
Code, hereinafter referred to as “this code”. |
- |
pdf_text |
| 101.2 |
101.2 Scope.
The provisions of this code shall apply to the construction, alteration, movement,
enlargement, replacement, repair, equipment, use and occupancy, location,
maintenance, removal and demolition of every building or structure or any
appurtenances connected or attached to such buildings or structures.
Exceptions: |
- |
pdf_text |
| 101.2.1 |
101.2.1 Appendices
Delete appendices A, B, D, J, and K.
Appendices C, E, F, G, H, I apply.
Delete IBC 101.4, and 101.4.1 through 101.4.7 Referenced Codes in its entirety and
substitute the following: |
- |
pdf_text |
| 101.4 |
101.4. Referenced Codes.
The other codes listed in Sections 101.4.1 through 101.4.7 and referenced
elsewhere in this code shall be considered part of the requirements of this code to
the prescribed extent of each such reference. |
- |
pdf_text |
| 101.4.1 |
101.4.1 Electrical.
The provisions of Rhode Island Electrical Code SBC-5-2006 shall apply
wherever referenced in this code as the ICC Electrical Code, and shall apply to
the installation of electrical systems, including alterations, repairs, replacement,
equipment, appliances, fixtures, fittings and appurtenances thereto.
SBC-1 2010
- 1 |
- |
pdf_text |
| 101.4.2 |
101.4.2 Gas.
The provisions of the Rhode Island Fuel Gas Code SBC-19-2010 shall apply
wherever referenced in this code as the International Fuel Gas Code, and shall
apply to the installation of gas piping from the point of delivery, gas appliances
and related accessories as covered in this code. These requirements apply to gas
piping systems extending from the point of delivery to the inlet connections of
appliances and the installation and operation of residential and commercial gas
appliances and related accessories. |
- |
pdf_text |
| 101.4.3 |
101.4.3 Mechanical.
The provisions of the Rhode Island Mechanical Code SBC-4-2010 shall apply
wherever referenced in this code as the International Mechanical Code and shall
apply to the installation, alterations, repairs and replacement of mechanical
systems, including equipment, appliances, fixtures, fittings and/or appurtenances,
including ventilating, heating, cooling, air-conditioning and refrigeration systems,
incinerators and other energy-related systems. |
- |
pdf_text |
| 101.4.4 |
101.4.4 Plumbing.
The provisions of Rhode Island Plumbing Code SBC-3-2010 shall apply whereve
referenced in this code as the International Plumbing Code, and shall apply to the
installation, alteration, repair and replacement of plumbing systems, including
equipment, appliances, fixtures, fittings and appurtenances, and where connected
to a water or sewage system and all aspects of a medical gas system. |
- |
pdf_text |
| 101.4.5 |
101.4.5 Property Maintenance.
The provisions of the Rhode Island State Property Maintenance Code SBC-6- |
- |
pdf_text |
| 101.4.6 |
101.4.6 Fire Prevention Code.
The provisions of or references to the International Fire Code 2009 edition shall
be cross referenced to the appropriate section of the Rhode Island Uniform Fire
Code. The chapters referencing construction standards will apply to either the
Rhode Island Uniform Fire Code Standards {RIGL 23-28.01 et seq}. as
referenced and amended NFPA 1 and NFPA 101 and those standards will apply
when this code references such a section or requirement. These cross-references
are not intended to impose any enforcement requirements on state or local fire
officials, and any conflicts with the State Fire Safety Codes shall be resolved in
favor of the more strict standard, and that standard shall be enforced by the
appropriate designated authority having jurisdiction. |
- |
pdf_text |
| 101.4.7 |
101.4.7 Energy.
The provisions of the Rhode Island Energy Code SBC-8-2010 shall apply
wherever referenced in this code as International Energy Conservation Code, and
shall apply to all matters governing the design and construction of buildings for
energy efficiency.
SBC-1 2010
- 2 |
- |
pdf_text |
| 10T |
10TH EDITION |
- |
pdf_text |
| 11 |
11.
Certification of Building Officials,
Building, Electrical, Plumbing and Mechanical
Inspectors
SBC-11-2010 |
- |
pdf_text |
| 111.4.2 |
111.4.2 Height:
The accessible urinal shall be stall-type or wall-hung with an elongated rim at a
maximum of 15 inches (15” = 381mm) above the finish floor. |
- |
pdf_text |
| 1111.1 |
1111.1 Children’s Water Closets:
Where provided, at least one shall comply with the following: |
- |
pdf_text |
| 1111.2 |
1111.2 Children’s Grab Bars |
- |
pdf_text |
| 1111.2.1 |
1111.2.1 The water closet
shall have two grab bars, 42 inches (42” = 1067mm) long, one mounted on the
wall in back of the water closet and one on the side wall closest to the water close
and located no more than six inches (6” = 152mm) from the interior corner
Where a tank prevents location of the rear grab bar, a bar may be installed three
SBC-1 2010
- 12 |
- |
pdf_text |
| 1111.2.2 |
1111.2.2 Height:
A grab bar shall be mounted from the floor to the top of the grab bar as follows: |
- |
pdf_text |
| 1111.2.3 |
1111.2.3 Thickness:
the outside diameter of grab bars shall be as follows: |
- |
pdf_text |
| 1111.3 |
1111.3 Children’s Sink
Where provided at least one sink including vanities shall comply with the
following: |
- |
pdf_text |
| 1111.3.1 |
1111.3.1 Clear floor space:
A clear floor space complying with ICC/ANSI A117.1-2003-606.2 be provided in
front of a sink to allow a forward approach. The clear floor space shall be on an
accessible route and shall extend no more than a maximum of 19 inches (19” = |
- |
pdf_text |
| 1111.3.2 |
1111.3.2 Height:
Sinks shall be mounted with the rim no higher than 30 inches (30” = 762mm)
above the finish floor. A clearance of at least 25 inches (25” = 635mm) above the
finish floor to the bottom of the apron shall be provided. Knee and toe clearance
shall be at least 30 inches (30” = 762mm) wide and 19 (19” = 483mm) deep. |
- |
pdf_text |
| 1111.3.3 |
1111.3.3 Piping:
Sink traps and drains shall be located as close to rear walls as possible. Hot water
and drainpipes exposed under sinks shall be recessed, insulated, or guarded. Ther
shall be no sharp or abrasive surfaces under sinks. |
- |
pdf_text |
| 1111.3.4 |
1111.3.4 Faucets:
Faucets shall be operable with one hand and shall not require tight grasping,
pinching, or twisting of the wrist. Lever-operated push-type, touch-type, or
electronically controlled mechanisms are acceptable designs. If self-closing
valves are used, the faucet shall remain open for at least ten seconds. |
- |
pdf_text |
| 1111.4 |
1111.4 Children’s Urinals |
- |
pdf_text |
| 1111.4.1 |
1111.4.1 Urinals:
Where one or more urinal is provided, at least one urinal shall be accessible.
SBC-1 2010
- 13 |
- |
pdf_text |
| 1111.4.3 |
1111.4.3 Flush Controls:
Flush controls shall be a hand operated or automatic, and shall be mounted no
more than 30 inches (30” = 762mm) above the flush floor. |
- |
pdf_text |
| 1111.5 |
1111.5 Children’s Mirror.
The top of any shelf and or bottom of any mirror which is provided above a sink
shall be set with the bottom edge of the reflecting surface no higher than 31
inches (31” = 787mm) above the finish floor.
Children’s Dispensers:
Towel dispensers, drying devices, or other types of devices and dispensers shall
have at least one of each device mounted within the zone of reach, and at least
one of each device shall be located within reach of a person using the accessible
sink. |
- |
pdf_text |
| 1111.7 |
1111.7 Children’s Controls and Receptacles.
If controls, receptacles, or other equipment are provided, then at least one of each
shall be mounted no higher than 36” inches (36” = 914mm) above the floor to the
centerline of the operable portion of the control.
SBC-1 2010
- 14 |
- |
pdf_text |
| 114.3 |
114.3, 115.1, 115.2, 115.3, 116.1, 116.2, 116.3, 116.4, 116.5.
All other Administrative provisions shall remain in effect. To the extent that ther
is an apparent conflict between the provisions of these administrative sections and
RIGL 23-27.3 101.0 et al, the provisions of state law shall prevail. Where other
provisions of this code refer to provisions of Chapter 1 Administration, Chapter I
Administration, or RIGL 23-27.3-101.0 et al shall apply as appropriate.
SBC-1 2010
- 3 |
- |
pdf_text |
| 12 |
12.
New Materials and Methods of Construction
SBC-12 |
- |
pdf_text |
| 127.0 |
127.0 the Building Official shall issue a permit for temporary construction as approved
by the Board of Appeal. Such permits shall be limited as to time of service but such
temporary construction shall not be permitted for more than one (1) year.
The building official shall be permitted to issue permits for temporary construction
limited to buildings of less than four hundred (400) square feet and all construction
trailers. Such permits shall be limited as to time of service but no such construction shall
be permitted to remain in place for more than one (1) year or the time scheduled for the
construction project. |
- |
pdf_text |
| 128.2.2 |
128.2.2, except as modified by the authority enforcing this Code, or by the Board for
Registration of Professional Engineers. |
- |
pdf_text |
| 13 |
13.
State Building Code for Existing Schools
SBC-13 |
- |
pdf_text |
| 1301 |
1301. Criteria.
Buildings shall be designed in accordance with the Rhode Island Energy Code
SBC 8-2010.
SBC-1 2010
- 15 |
- |
pdf_text |
| 1301.1 |
1301.1 Scope.
This chapter governs the design and constructions of buildings for energy efficiency. |
- |
pdf_text |
| 14 |
14.
Property Maintenance Code
SBC-14 |
- |
pdf_text |
| 1405.1.1 |
1405.1.1 Re-siding Exterior Walls.
Materials and methods of application used for re-siding or replacing an existing
wall covering shall comply with the requirements of this section. New Exterior
side wall covering shall not be installed without first removing existing wall
coverings when any of the following conditions occur: |
- |
pdf_text |
| 1406.3 |
1406.3 Balconies and similar projections.
Balconies and similar projections of combustible construction, other than fire-retardant-
treated wood, shall afford the fire-resistance rating required by Table 601 for floor
construction or shall be of Type IV construction as described in Section 602.4, and the
aggregate length shall not exceed 50 percent of the building perimeter on each floor.
Exceptions: |
- |
pdf_text |
| 1608.1 |
1608.1 General.
Design snow loads shall be determined in accordance with Section 7 of ASCE 7
using the ground snow load values determined by Table 1608.1, but the minimum
flat roof snow load shall be not less than that determined by Table 1608.1. The
design roof load shall not be less than that determined by Section 1607.
Delete section 1608.2 Ground Snow Load. |
- |
pdf_text |
| 1608.1 (cont. 2) |
Add the following new section to IBC Section 1608 Snow Loads.
Structural Loads.
When a new building is to be constructed or an existing building extended to
greater height than an existing adjoining building, a determination of structura
integrity of the roof of the adjoining building shall be made regarding the snow load
in accordance with Section 1608.0 SNOW LOADS. The person intending to caus
the construction or building height extension shall deliver written notice of intent t
the owner of the potentially affected building. The notice shall request license t
enter the potentially affected building to inspect and determine the existing building'
capacity to sustain additional imposed snow drift load. The person causing suc
construction shall be liable and shall at their own expense preserve, protect and, i
necessary, reconstruct those portions of the adjacent building affected by thi
construction. If the owner of the adjacent building refuses to allow inspection
protection or reconstruction as may be required, the person causing such ne
construction or building height extension shall notify, in writing, both the Buildin
Official and the owner of the adjacent property. Such notification shall identify tha
the responsibility of providing inspection, protection or reconstruction to the adjacen
building has become the exclusive responsibility of the owner of the adjacen
property.
Delete section 1609.3 Basic Wind Speed and substitute the following: |
- |
pdf_text |
| 1609.3 |
1609.3 Basic Wind Speed.
The basic wind speed, in mph, shall be determined by Rhode Island Wind Speed Map
Figure 1609 and Table 1608.1.
Delete all IBC Figures 1609 and substitute Rhode Island Wind Speed Map Figure 1609
and Figure 1609 (A).
SBC-1 2010
- 19 |
- |
pdf_text |
| 1613.5.1 |
1613.5.1 Acceleration parameters.
The parameters SS and S1 for each Rhode Island community are given in Table 1608.1.
SBC-1 2010
- 20 |
- |
pdf_text |
| 17 |
17.
Public Buildings Accessibility Meeting Standards
SBC-17 |
- |
pdf_text |
| 18 |
18.
Native Lumber
SBC-18 |
- |
pdf_text |
| 18 |
18” = 381mm to 457mm) for fourth grade to sixth grade. The water closet shall
also be located 42 inches (42” = 1067mm) from the centerline of the water closet
to the opposite wall or closest edge of next fixture. |
- |
pdf_text |
| 1801.3 |
1801.3 Frost protection.
Except where otherwise protected from frost, foundation walls, piers and other permanen
supports of buildings and structures shall be protected by on or more of the following
methods: |
- |
pdf_text |
| 19 |
19.
Fuel Gas Code
SBC-19-2010
SBC-1 2010
- 1 |
- |
pdf_text |
| 2 |
2. Throughout every portion of educational buildings below the lowest level of
exit discharge serving that portion of the building.
Exception: An automatic sprinkler system is not required in any area below the
lowest level of exit discharge serving that area where every classroom
throughout the building has at least one exterior exit door at ground level. |
- |
pdf_text |
| 2 |
2.
Fire pumps. |
- |
pdf_text |
| 2 |
2.
Fastening systems tested by the manufacturer to 110 MPH shall be permitted to
be installed in any wind zone.
SBC-1 2010
- 18 |
- |
pdf_text |
| 2 |
2. Construction in accordance with ASCE 32; 05 |
- |
pdf_text |
| 2 |
2. livestock shelters arts/crafts, flea markets, etc. of limited duration consisting of
small booths and multiple vendors, and as may be properly licensed by the
municipality. |
- |
pdf_text |
| 2 |
2.
Area of 600 Square feet (56 M2) or less for light-frame
construction or 400 square feet (37 m2) or less for other than light-
frame construction; and |
- |
pdf_text |
| 2 |
2. Multiplier factor for Thickness=
.20 |
- |
pdf_text |
| 2 |
2. Location: The centerline of the water closet shall be located 11 inches (11” = 279
mm) from the nearest side wall for pre-kindergarten; 11 to 15 inches (11” to 15” |
- |
pdf_text |
| 2 |
2.
The providing mill shall certify in writing to the consumer or builder on a
form to be provided by the State Building Code Standards Committee that the
quality and safe working stresses of such lumber are equal to or exceed No. 2
grade in accordance with grading practices established by an approved lumber
grading or approved testing agency.
Exception: Load bearing walls shall be of stud grade minimum.
This certification shall be filed with the local building official having
jurisdiction as part of the building permit application; |
- |
pdf_text |
| 2 |
2.
Untreated wood is permitted for pickets and rails, or similar guardrail devices that
are limited to 42 inches (1067 mm) in height. |
- |
pdf_text |
| 2 |
2.
Entertainment by a live band or recorded music generating above-normal
sounds |
- |
pdf_text |
| 2 |
2..
One and Two Family Dwelling Code
SBC-2-2010 |
- |
pdf_text |
| 2 |
2.
Existing buildings undergoing repair, alterations or additions and changes
of occupancy shall comply with the provisions of this code or the State
Rehabilitation Code SRC-1-2002 (see RIGL 23-27.3-106.0). |
- |
pdf_text |
| 2 |
2.
When the existing wall has three (3) or more applications of any wall covering.
Exception: The total number of wall coverings shall not be limited when any of
the existing wall coverings consists of asbestos cement board or asbestos cement
shingles or any protective encapsulating or protective siding/layer immediately
over the asbestos material. |
- |
pdf_text |
| 2 |
2.
Stress increases: Lumber which is sized in excess of the dimensions established b
the AF&PA NDS-01 for the given nominal size referenced shall be allowed to hav
increased loads providing structural calculations are submitted verifying suc
increases. See Table 2309. |
- |
pdf_text |
| 2 |
2.
The fire area has an occupant load of 300 or more. |
- |
pdf_text |
| 2010 |
2010.
In order to assure public access to this code the Office of the State Building Code Commissioner
shall provide a copy of this code to the Rhode Island State Library, which is located on the
second floor of the State House. In addition, all codes may be viewed during business hours at
the Department of Administration’s Library which is located on the fourth floor of the William E.
Powers Building, One Capitol Hill, Providence.
The Legislative Regulation Committee approved adoption of this code on March 4, 2010
.
By:
John P. Leyden
Executive Secretary
Rhode Island Building Code Standards Committee
SBC-1 2010
- 1 |
- |
pdf_text |
| 2010 |
2010 Provides requirements for continued use and maintenance buildings and
property, and of related plumbing, mechanical, electrical and fire protection
systems in existing residential and non-residential structures. |
- |
pdf_text |
| 2106.1 |
2106.1 Seismic design requirements for masonry.
Masonry structures and components shall comply with the requirements in Section |
- |
pdf_text |
| 23 |
23, Chapter 23-27.3, Section 109.1, paragraphs a through c inclusive, has formally adopted and
promulgated as the Rhode Island State Building Code, the provisions of the International
Building Code, 2009 edition, as published by the International Code Council, Inc. (I.C.C.),
together with amendments thereto hereinafter set forth to the articles and sections of this code:
The provisions of Title 23, Chapter 27.3 of the General Laws of Rhode Island establishing
administration and enforcement are hereby incorporated by reference. Regulatory Administratio
Chapter 1 immediately follows and is supplemental to the General Laws.
Editorial Note: Code users please note:
When purchasing or using the IBC 2009 code, please take note of the particular printing edition.
Errata to that printing edition is available on-line directly at no charge at
www.iccsafe.org/cs/codes/pages/errata.aspx or call the office of the State Building Code
Commissioner at 401-222-1129 for further information.
Printed copies of the administrative and enforcement provisions of Title 23, Chapter 27.3 are
available at the Office of the State Building Code Commission or on-line at
http://www.rilin.state.ri.us/Statutes/TITLE23/23-27.3/INDEX.HTM |
- |
pdf_text |
| 23 (cont. 2) |
The International Building Code, 2009 Edition, is protected by the copyright that has been issued
to the ICC. As a result, the State Building Code is not available in complete form to the public in
an electronic format. The International Building Code 2009 edition that is referred to within is
contained in a printed volume and is also in an electronic format that have been published by the
ICC under an exclusive license.
The Office of the State Building Code Commissioner has purchased volumes of these codes and
they shall be distributed to Rhode Island cities and towns during the month of June 2010 so that
local officials will have access to the code prior to the implementation of these rules on July 1, |
- |
pdf_text |
| 2309 |
2309 Native Lumber. |
- |
pdf_text |
| 2309.1 |
2309.1 Scope:
The provisions of this section shall govern the use of Native Lumber in accordance with
RIGL23-27.3-109.0 of the State Building Code.
Native Lumber is unmarked structural lumber from wood processed in the State of Rhod
Island by a mill registered in accordance with provisions of this code.
Such lumber which is not grade marked or certified by a recognized grading organization
designated under Section 2303.1.1 shall be classified as an ordinary material and is not
required to meet the test requirement of section 1710.2 and shall be permitted for use as
follows. |
- |
pdf_text |
| 2309.2 |
2309.2 Identification and Use: |
- |
pdf_text |
| 2309.3 |
2309.3 Native Softwoods and Hardwoods
Native hardwood or softwood lumber may be used in post and beam timber typ
construction per section 602.4. Such uses as beam, girders, headers, and column support
will require engineering evaluation for the allowable design values and duration of loadin
factors for all buildings other than One & Two Family Dwellings.
Native lumber located near or in contact with the ground shall be naturally durable o
pressure-treated in accordance with the provisions of section 2304.11. |
- |
pdf_text |
| 2309.4 |
2309.4 Sizing Criteria for Native Softwood Lumber |
- |
pdf_text |
| 2309.5 |
2309.5 Moisture Content
The moisture content for structural framing shall be 19% or less unless the produce
indicates that the lumber is surfaced green. |
- |
pdf_text |
| 2309.6 |
2309.6 Post and Beam Type Structures
Native hardwood and softwood lumber are permitted in post and beam timber-typ
structures. Design drawings and calculation shall be by a Rhode Island registered architec
or engineer and submitted to the building official for approval. |
- |
pdf_text |
| 2309.7 |
2309.7 Responsibilities
The building official shall indicate the use of native lumber on the building permi
application under the heading “Description of work to be performed” and also the name o
the mill providing the native lumber.
The building official shall have the right to reject any lumber of questionable quality base
on visual observation.
SBC-1 2010
- 28 |
- |
pdf_text |
| 24 |
24-hour basis and who are incapable of self-preservation or who are harmful to
themselves or others.
Hospitals and Mental Hospitals
Buildings or portions thereof used on a 24-hour basis for the medical, psychiatric
obstetrical or surgical treatment of inpatients who are incapable of self-
preservation.
Nursing Homes
Nursing homes are long-term care facilities on a 24-hour basis, including both
intermediate care facilities and skilled nursing facilities, serving more than five
persons and any of the persons are incapable of self-preservation.
Delete IBC 308.5 I-4 Day Care Facilities and substitute the following: |
- |
pdf_text |
| 2701.1 |
2701.1 Scope.
This chapter governs the electrical components, equipment and systems used in building
and structures covered by this code. Electrical components, equipment and systems shal
be designed and constructed in accordance with the provisions of SBC-5-2008.. |
- |
pdf_text |
| 2701.2 |
2701.2 Permits.
Electrical wiring including elevators and other conveyances as regulated by th
Department of Labor and Training, or data, telecommunications, video and soun
installations, shall not be installed in a building or structure, nor shall alteration of a
existing electrical wiring system be made until a permit has been issued therefor a
required in Section GL 23-27.3-113.3.1.
Exception: Work not covered in SBC-5-2008 section 90.2(b) 1-5 inclusive. As
used in section 4 & 5 a “utility” is a company or business regulated and/or
licensed by the Rhode Island Public Utilities Commission. Subcontractors
employed by a utility are not exempt from permit requirements unless the
proposed work is being performed in the public right-of-way or within public
utility easements. It shall be unlawful to use or allow the use of, or to supply
current for, an electrical system in a building or structure, or to allow the use of,
or to supply current for data, telecommunications, video or audio installations
unless the required permits have been issued and approved by the authority
having jurisdiction. |
- |
pdf_text |
| 2701.3 |
2701.3 Certification.
Except for use group R (residential use), construction documents shall bear the seal of a
Registered Professional Engineer who shall provide the services as required by 23-27.3- |
- |
pdf_text |
| 2701.4 |
2701.4 Re-inspection.
An electrical installation from which an electrical service has been discontinued for a
period of thirty (30) days or more shall not have service restored until the system has
been re-inspected and a new certificate of inspection issued.
Exception: Re-inspection of dwelling units shall only be required if the electrica
service has been discontinued for a period of one year.
SBC-1 2010
- 31 |
- |
pdf_text |
| 2701.5 |
2701.5 Emergency generators for Housing for the Elderly. All housing for the
elderly complexes, as defined in § 42-66.1-2 which are serviced by one or more
elevators and/or electrically powered chair lifts, and which include more than on
hundred fifty (150) residential living units in a single building shall be equipped
with emergency generators which shall provide sufficient power to provide
emergency lighting to all common areas and a community room and power to
operate the elevators and a refrigerator in a common area. Generator systems
shall be in accordance with the national electric code and § 23-28.24-9. |
- |
pdf_text |
| 2701.5 |
2701.5 Reference
The following section is taken directly from current R.I. General Laws (RIGL 42-66.9-1)
for references purposes only: |
- |
pdf_text |
| 2701.6 |
2701.6 References.
Where this code references other ICC codes, use the appropriate regulation as adopted by
the State of Rhode Island and SBC-5-2008 for the IEC. References to the International
Fire Code (IFC) and its requirements are deleted, and refer to the R.I. State Fire Safety
Code for requirements and enforcement by that authority having jurisdiction. |
- |
pdf_text |
| 2701.7 |
2701.7 Other Codes.
The Rhode Island Uniform Fire Safety Code contains provisions for specific wiring
methods for fire alarms, signaling systems, and other building fixtures such as exit
signage, emergency lighting, and emergency and standby power systems among others.
Refer to the latest editions of that code for the latest provisions. |
- |
pdf_text |
| 2702.1 |
2702.1 Installation. Emergency and standby power systems shall be installed in
accordance with the SBC-5-2008, NFPA 110 and NFPA 111. |
- |
pdf_text |
| 2702.2 |
2702.2 Where required. Emergency and standby power systems shall be provided
where required by Sections 2702.2.1 through 2702.2.19. |
- |
pdf_text |
| 2702.2.1 |
2702.2.1
Group A Occupancies.
Emergency power shall be provided for voice communication systems in Group A
occupancies in accordance with Section 907.2.1.2. |
- |
pdf_text |
| 2702.2.10 |
2702.2.10 Highly toxic and toxic materials. Emergency power shall be
provided for occupancies with highly toxic to toxic materials in accordance with
the International Fire Code and Rhode Island State Fire Safety Codes. |
- |
pdf_text |
| 2702.2.11 |
2702.2.11 Organic peroxides. Standby power shall be provided for occupancies
with organic peroxides in accordance with the International Fire Code and Rhode
Island State Fire Safety Codes. |
- |
pdf_text |
| 2702.2.12 |
2702.2.12 Pyrophoric materials. Emergency power shall be provided for
occupancies with pyrophoric materials in accordance with the International Fire
Code and Rhode Island State Fire Safety Codes. |
- |
pdf_text |
| 2702.2.13 |
2702.2.13 Covered mall buildings. Covered mall buildings exceeding 50,000
square feet (4645 m2) shall be provided with standby power systems which are
capable of operating the emergency voice/alarm communication. |
- |
pdf_text |
| 2702.2.14 |
2702.2.14 High rise buildings. Emergency and standby power shall be provided
in high rise buildings in accordance with Chapter 27 and for the items listed
below: |
- |
pdf_text |
| 2702.2.15 |
2702.2.15 Underground buildings. Emergency and standby power shall be
provided in underground buildings in accordance with Sections 405.9 and 405.10. |
- |
pdf_text |
| 2702.2.16 |
2702.2.16 Group I-3 occupancies. Emergency power shall be provided for
SBC-1 2010
- 33 |
- |
pdf_text |
| 2702.2.17 |
2702.2.17 Airport traffic control towers. Standby power shall be provided in
airport traffic control towers in accordance with Section 412.1.5. |
- |
pdf_text |
| 2702.2.18 |
2702.2.18 Elevators. Standby power for elevators shall be provided as set forth
in Section 3003.1. |
- |
pdf_text |
| 2702.2.19 |
2702.2.19 Smoke proof enclosures. Standby power shall be provided for
smoke proof enclosures as required by Section 909.20. |
- |
pdf_text |
| 2702.2.2 |
2702.2.2 Smoke control systems. Standby power shall be provided for smoke
control systems in accordance with Section 909.11. |
- |
pdf_text |
| 2702.2.3 |
2702.2.3 Exit signs. Emergency power shall be provided for exit signs in
accordance with Section 1003.2.10.5. |
- |
pdf_text |
| 2702.2.4 |
2702.2.4 Means of egress illumination. Emergency power shall be provided for
means of egress illumination in accordance with Section 1003.2.11.2.
SBC-1 2010
- 32 |
- |
pdf_text |
| 2702.2.5 |
2702.2.5 Accessible means of egress elevators. Standby power shall be
provided for elevators that are part of an accessible means of egress in accordance
with Section 1003.2.13.3. |
- |
pdf_text |
| 2702.2.6 |
2702.2.6 Horizontal sliding doors. Standby power shall be provided for
horizontal sliding doors in accordance with Section 1003.3.1.3.3. |
- |
pdf_text |
| 2702.2.7 |
2702.2.7 Semiconductor fabrication facilities. Emergency power shall be
provided for semiconductor fabrication facilities in accordance with Section |
- |
pdf_text |
| 2702.2.8 |
2702.2.8 Membrane structures. Standby power shall be provided for auxiliary
inflation systems in accordance with Section 3102.8.2. Emergency power shall b
provided for exit signs in temporary tents and membrane structures in accordance
with the International Fire Code. |
- |
pdf_text |
| 2702.2.9 |
2702.2.9 Hazardous materials. Emergency or standby power shall be provided
in occupancies with hazardous materials in accordance with Section 414.5.4. |
- |
pdf_text |
| 2702.3 |
2702.3 Maintenance. Emergency and standby power systems shall be maintained
and tested in accordance with the Rhode Island State Fire Safety Codes.
Rev. eff. 1/06
SBC-1 2010
- 34 |
- |
pdf_text |
| 279 |
279 mm to 381mm) for kindergarten to the third grade and 15 to 18 inches (15” to |
- |
pdf_text |
| 2801.1 |
2801.1 Scope.
Mechanical appliances, equipment and systems shall be constructed, installed and
maintained in accordance with SBC-4-2010 the Rhode Island Mechanical Code and
SBC-19-2010 the Rhode Island Fuel Gas Code. Masonry chimneys, fireplaces and
barbecues shall comply with the Rhode Island Mechanical Code and Chapter 21 of this
code.
SBC-1 2010
- 35 |
- |
pdf_text |
| 2901.1 |
2901.1 Scope.
The provisions of this chapter and SBC-3-2010 the Rhode Island Plumbing Code shall
govern the erection, installation, repairs, relocation, replacement, addition to, use or
maintenance or plumbing equipment and systems.
SBC-1 2010
- 36 |
- |
pdf_text |
| 3 |
3. Any structure less than 100 sq. ft. |
- |
pdf_text |
| 3 |
3.
Eave height of 10 feet (3048 mm) or less
Footings shall not bear on frozen soil unless such frozen condition is of a permanent
character.
SBC-1 2010
- 25 |
- |
pdf_text |
| 3 |
3’-4”
East Providence |
- |
pdf_text |
| 3 |
3. Height: Water closets shall be set at a height measured from the floor to the top
of the seat as follows: |
- |
pdf_text |
| 3 |
3.Operating stress F’s = 1.25 x Fs
F’s = 1.25 x 1,000 = 1,250
Sum = 1.25 |
- |
pdf_text |
| 3 |
3.
Later-than average operating hours |
- |
pdf_text |
| 3 |
3.
Construction Types 3A and 5A are not required to meet the provisions of this
section.
SBC-1 2010
- 16 |
- |
pdf_text |
| 3 |
3.
Emergency voice/alarm communication systems. |
- |
pdf_text |
| 3 |
3.
Plumbing Code
SBC-3-2010 |
- |
pdf_text |
| 3 |
3.
Asbestos cement board or asbestos cement shingles and any protective
encapsulating layer thereupon shall not be required to be removed unless the
existing wall is unacceptable for use as a base for additional layers of wall
covering. |
- |
pdf_text |
| 3 |
3’-4”
West Greenwich |
- |
pdf_text |
| 3 |
3. Erecting on solid rock
Exception: Free-standing buildings meeting all of the following conditions shall
not be required to be protected: |
- |
pdf_text |
| 3 |
3.
Native Lumber shall be limited to the following uses:
a. One and two-family dwellings not exceeding three stories in height, or:
b. General building construction types 3B, 4 or 5B not exceeding ten
thousand square feet of cumulative floor area or 35 feet in height, but not
to exceed 2 stories, or:
c. Those low stress buildings not intended for human habitation such as
barns, sheds, agricultural, detached garages, outbuildings and other
accessory structures; or
SBC-1 2010
- 27 |
- |
pdf_text |
| 3 |
3.
The fire area is located on a floor other than the level of exit discharge. |
- |
pdf_text |
| 3 |
3’-4”
North Providence |
- |
pdf_text |
| 3 |
3’-4”
New Shoreham |
- |
pdf_text |
| 3 |
3’-4”
North Kingstown |
- |
pdf_text |
| 3-1 |
3-1/8 =
increase of |
- |
pdf_text |
| 3001.1 |
3001.1 SCOPE
Except as may otherwise be provided by statute, the provisions of this chapter shall
control the design, construction and installation of all special hoisting and conveying
equipment hereafter installed, relocated or altered in all buildings or structures. The
design, construction, installation, maintenance, relocation and operation of all elevators,
dumbwaiters, moving stairways, moving walks, and certain elevating devices used to
handle materials only, shall be subject to the rules and regulations adopted and enforced
by the Rhode Island Department of Labor and Training, Division of Occupational Safety,
Elevator Unit. Portable elevating devices not covered by this chapter or by the
Department of Labor, shall be constructed, operated and maintained in compliance with
accepted engineering practice.
Delete IBC 3001.2 Referenced standards and substitute the following: |
- |
pdf_text |
| 3001.1.1 |
3001.1.1 PERMITS:
Permits for the installation of elevators, dumb waiters, moving stairways, moving walks,
and certain elevating devices used to transport materials and personnel shall be issued
only by the Department of Labor and Training, Division of Occupational Safety, Elevato
Unit. Permits for all other devices shall be issued by the building official.
SBC-1 2010
- 37 |
- |
pdf_text |
| 305.2 |
305.2 Day Care.
The use of a building or structure, or portion thereof, for educational, supervision
or personal care services for more than eight children older than 2-1/2 years of
age, shall be classified as a Group E occupancy.
Delete IBC sections 308.2 Group I-1 and substitute the following: |
- |
pdf_text |
| 308.2 |
308.2 Group I-1.
This occupancy shall include buildings, structures, or parts thereof housing more
than sixteen persons, on a 24-hours basis, who because of age, mental disability or
other reasons, live in a supervised residential environment that provides personal
care services. The occupants are capable of responding to an emergency situation
without physical assistance from staff. This group shall include, but not be limited
to, the following:
Residential board and care facilities
Assisted living facilities
Halfway houses
Group homes
Congregate care facilities
Social rehabilitation facilities
Alcohol and drug centers
Convalescent facilities
A facility such as the above with eight or fewer persons shall comply with the
International Residential Code in accordance with Section 101.2. A facility such
as above, housing at least nine and not more than 16 persons, shall be classified as
Group R-4.
Delete IBC section 308.3 Group I-2 and substitute the following: |
- |
pdf_text |
| 308.3 |
308.3 Group I-2.
This occupancy shall include buildings and structures used for medical, surgical,
psychiatric, nursing or custodial care on a 24-hour basis of more than eight persons
who are not capable of self-preservation. This group shall include, but not be
limited to, the following:
Child Care Facilities
Hospitals
Nursing homes (both intermediate-care facilities and skilled nursing facilities)
Mental hospitals
Detoxification facilities
SBC-1 2010
- 5 |
- |
pdf_text |
| 308.3.1 |
308.3.1 Child Care Facility
Facility that provides care on a 24-hour basis to more than eight children 2 ½
years of age or less.
Detoxification Facilities
Facilities that serve patients who are provided treatment for substance abuse on a |
- |
pdf_text |
| 308.5 |
308.5 Group I-4, Day Care Facilities.
This group shall include buildings and structures occupied by persons of any age
who receive custodial care for less than 24 hours by individuals other than parents
or guardians, relatives by blood marriage or adoption, and in a place other than
the home of the person cared for. A facility such as the above with eight or fewer
persons shall be classified as a Group R-3 or shall comply with International
Residential Code in accordance with Section 101.2. Places of worship during
religious functions are not included.
Delete IBC 308.5.2 Child Care Facility and substitute the following: |
- |
pdf_text |
| 308.5.2 |
308.5.2 Child Day Care Facility
A facility that provides supervision and personal care on less than a 24-hour basis
for more than eight children 2-1/2 years of age or less shall be classified as Group
I-4.
Exception: A child day care facility that provides care for more than eight but no
more than 100 children 2-1/2 years or less of age, when the rooms where such
children are cared for are located on the level of exit discharge and each of these
child care rooms has an exit door directly to the exterior, shall be classified as
Group E.
SBC-1 2010
- 6 |
- |
pdf_text |
| 3103.0 |
3103.0 General:
Pursuant to a variance granted by the Board of Appeals under the provisions of Section |
- |
pdf_text |
| 3103.2 |
3103.2 Special Approval
All temporary construction, when intended to be occupied by the owner, employee, or
general public shall conform to structural strength, fire safety, means of egress, light,
ventilation and sanitary requirements of the Code necessary to insure the public health,
safety and general welfare. |
- |
pdf_text |
| 3103.3 |
3103.3 Termination of Approval
The building official is hereby authorized to terminate such special approval and to order
demolition and/or removal of any such construction at his discretion.
Add the following new section to Chapter 31 |
- |
pdf_text |
| 3110.1 |
3110.1 Definition
Fabric Structures are structures utilizing wood, metal or plastic frames and covered with
cloth, canvas or plastic material, excluding tents, agricultural and horticultural
greenhouses, and furnishings such as umbrellas, awnings and canopies or portable shade
canopies. |
- |
pdf_text |
| 3110.2 |
3110.2 Fabric Structures:
Fabric Structures: Fabric Structures shall be located in accordance with applicable local
zoning code provisions. Permits shall be required for all fabric structures. Fabric
structures less than 400 sq. ft. in area and installed for a period not exceeding 1 year shall
be installed in accordance with manufacturer’s installation instructions. Fabric structures
greater than 400 sq. ft. in area or intended to be in place for a period exceeding 12 month
shall only be approved pending a satisfactory decision by the state or local Building Code
Board of Appeals, unless full code compliance for permanent structures in all respects is
demonstrated to the satisfaction of the local building official. The State Fire Marshal or
SBC-1 2010
- 38 |
- |
pdf_text |
| 3304.2 |
3304.2 Final Grading.
Lots shall be graded so that surface accumulation of water does not occur across
adjoining property. Retaining walls, which may be necessary to prevent surface run-off
into adjoining property, shall be constructed in accordance with this code and any
applicable ordinances. Storm drainage systems necessary to divert flows from adjoining
property shall be designed and installed in accordance with SBC-3 –2010 the Rhode
Island State Plumbing Code.
Add the following new section to IBC Section 3307 Protection of Adjoining Property: |
- |
pdf_text |
| 3307.2 |
3307.2 Structural Loads.
See Section 1608.10.
SBC-1 2010
- 40 |
- |
pdf_text |
| 3407.1 |
3407.1 Historic Buildings: |
- |
pdf_text |
| 3407.2 |
3407.2 Approval:
The provisions of this code relating to the construction, repair, alteration, enlargement,
restoration and moving of buildings or structures shall not be mandatory for existing
buildings or structures identified and classified by the state or local government authority
as historic buildings, subject to the approval of the Board of Appeals, when such
buildings are judged by the code official to be safe and in the interest of public health,
safety and welfare regarding any proposed construction, alteration, repair, enlargement
and relocation. All such approvals shall be based on the applicant's complete submission
of professional architectural and engineering plans and specifications bearing the
professional seal of the designer.
Delete IBC Section 3410.2 Applicability and substitute the following: |
- |
pdf_text |
| 3410.2 |
3410.2 Applicability
Existing buildings in which there is work involving additions, alterations or changes of
occupancy shall be made to conform to the requirements of this section or the provisions
of Sections 3403 through 3407. The provisions in Sections 3410.2.1 through 3410.2.5
shall apply to existing occupancies that will continue to be, or are proposed to be, in
Groups A, B, E, F, M, R, S and U. These provisions shall not apply to buildings with
occupancies in Group H or I.
SBC-1 2010
- 41 |
- |
pdf_text |
| 4 |
4.
Any disturbance, repair or removal of existing asbestos cement board or asbestos
cement shingles shall be in accordance with all State and Federal regulations.
Delete IBC Section 1406.3 exceptions 3 and 4 and substitute as follows: |
- |
pdf_text |
| 4 |
4. Flush Controls: Controls for flush valves on water closets used by children shall
be mounted on the wide side of water closet within 20 to 30 inches (20” to 30” = |
- |
pdf_text |
| 4 |
4’-6”
South Kingstown |
- |
pdf_text |
| 4 |
4.
Uses not permitted: Native lumber shall not be used in engineered plate-truss
systems unless such lumber is graded in accordance with Section 2303.1.1. |
- |
pdf_text |
| 4 |
4’-0”
Cranston (east of 295) |
- |
pdf_text |
| 4 |
4. Furnishings such as umbrellas awnings, etc.
SBC-1 2010
- 39 |
- |
pdf_text |
| 4 |
4’-0”
West Warwick |
- |
pdf_text |
| 4 |
4.
If the balcony is subject to deterioration as specified in section 2304.11.5, the
provisions of 2304.11.2 shall prevail in lieu of this section’s fireresistance
requirements for Types 3, 4 and 5 construction.
SBC-1 2010
- 17 |
- |
pdf_text |
| 4 |
4’-6”
*Line of Demarcation between 110 mph and 120 mph zones generally is Route 1A at Watch Hill in
Westerly; East to Route 1 through Westerly, Charlestown, and South Kingstown; thence Northerly
along Route 1 through Narragansett, to Easterly on South Ferry Road. See figures 1609 and 1609A.
SBC-1 2010
- 23 |
- |
pdf_text |
| 4 |
4.
Nightclubs with an occupancy load in a single fire area of more than 150
occupants (see also Chapter 2 Definitions: Nightclub).
Delete IBC 903.2.3 Group E and substitute the following
[F] 903.2.3 Group E.
An automatic sprinkler system shall be provided for Group E occupancies as follows: |
- |
pdf_text |
| 4 |
4.
Tables and seating (if any) arranged or positioned so as to create ill-
definable aisles |
- |
pdf_text |
| 4 |
4.
Lighting for mechanical equipment rooms. |
- |
pdf_text |
| 4 |
4’-6”
Central Falls |
- |
pdf_text |
| 4 |
4.
Mechanical Code
SBC-4-2010 |
- |
pdf_text |
| 4 |
4’-6”
Little Compton |
- |
pdf_text |
| 4 |
4 or 5 construction. |
- |
pdf_text |
| 4 |
4’-0”
Cranston (west of 295) |
- |
pdf_text |
| 4 |
4’-0”
North Smithfield |
- |
pdf_text |
| 4 |
4’-6”
East Greenwich |
- |
pdf_text |
| 401.2 |
401.2 Fire Alarm Systems.
The requirements herein prescribed for the design, operation and installation of fire alarm
systems, detection devices, suppression systems, communications systems, etc. shall be
construed as supplemental to any applicable provisions of Rhode Island State Fire Safety
Code. |
- |
pdf_text |
| 401.3 |
401.3 Fire Prevention Code.
The provisions of the International Fire Code 2009 Edition shall apply when this code
directly references a section or requirement. These cross-references are not intended to
impose any enforcement requirements on state and local fire officials, and any conflicts
with the State Fire Safety Codes shall be resolved in favor of the stricter standard, and
that standard shall be enforced by the appropriate designated authority having
jurisdiction.
Add the following new sections: |
- |
pdf_text |
| 421.1 |
421.1 Manufactured Homes.
Manufactured homes are constructed in accordance with the Federal Department of
Housing and Urban Development Part 3280 Manufactured Home Construction and
Safety Standards. Refer to Appendix E of SBC2-2010 the Rhode Island One and Two
Family Dwelling Code for specific provisions regarding permitting, foundation systems,
additions, site utility connections and foundation and anchorage details. |
- |
pdf_text |
| 422.1 |
422.1 Modular Construction.
Buildings and structures partially or completely constructed off-site shall be constructed
in conformance with this code or SBC-2-2010 the Rhode Island Residential One and Tw
Family Code as appropriate for the use and occupancy. Manufacturers shall be registered
with the Interstate Industrialized Building Commission (IIBC) and submit for approvals
and permits in accordance with RIGL 23-27.4 and IIBC Compact regulations.
SBC-1 2010
- 8 |
- |
pdf_text |
| 483 |
483 mm) underneath the sink. |
- |
pdf_text |
| 5 |
5.
Flexible fuel loading |
- |
pdf_text |
| 5 |
5. In passenger elevator shafts, pits and mechanical rooms. If provided, the
installation shall meet all requirements of this code, NFPA 13, the Rhode
Island Fire Safety Code and the Rhode Island Elevator Code.
Delete section 906 in its entirety and substitute the following: |
- |
pdf_text |
| 5 |
5. Toilet paper dispensers: Toilet paper dispensers used by children shall be
centered above finished floor, as follows: |
- |
pdf_text |
| 5 |
5.
Electrical Code
SBC-5-2008 |
- |
pdf_text |
| 508m |
508mm to 762mm) above the floor. |
- |
pdf_text |
| 6 |
6.
A specific area designated for dancing |
- |
pdf_text |
| 6 |
6.
Property Maintenance Code
SBC-6-2010 |
- |
pdf_text |
| 7 |
7.
Service facilities for alcoholic, beverages and food |
- |
pdf_text |
| 716.5.3 |
716.5.3 Shaft Enclosures:
Shaft enclosures in Use Group I and in High Rise structures are permitted to be
penetrated by ducts and air transfer openings and shall be protected with approved fire
conditions and smoke dampers installed in accordance with their listing. All other use
groups shaft enclosure penetrations shall be protected with approved fire dampers
installed in accordance with their listing.
Retain exceptions 1, 1.1,1.2,1.3,1.4 and delete exceptions 2,2.1,2.2 and 3.
SBC-1 2010
- 9 |
- |
pdf_text |
| 8 |
8.
Energy Conservation Code
SBC-8-2010 |
- |
pdf_text |
| 8 |
8.
Potential for consumption of legal or illegal drug use contributing to
delayed reaction time to emergency events |
- |
pdf_text |
| 9 |
9.
High occupant load density |
- |
pdf_text |
| 9 |
9
Enforcement and Implementation Procedures for
Projects Under the Jurisdiction of The State of
Rhode Island
SBC-9 |
- |
pdf_text |
| 901.8 |
901.8 Other Codes.
Provisions governing where fire protection systems are required are also contained in the
Rhode Island Fire Safety Code. The most restrictive provision of each code shall apply.
Delete IBC 903.2.1.2 Group A-2 and substitute the following: |
- |
pdf_text |
| 903.2.1.2 |
903.2.1.2 Group A-2.
An automatic sprinkler system shall be provided for Group A-2 occupancies where one
of the following conditions exists: |
- |
pdf_text |
| 906.1 |
906.1 General.
Portable Fire Extinguishers shall be provided in accordance with the Rhode Island
Uniform Fire Code.
Delete section 907 in its entirety and substitute the following:
SBC-1 2010
- 10 |
- |
pdf_text |
| 907.1 |
907.1 General.
FIRE ALARM AND DETECTION SYSTEMS shall be provided in accordance with the
Rhode Island Uniform Fire Code.
SBC-1 2010
- 11 |
- |
pdf_text |
| Note 1 |
Note 1.
Notation FS is the allowable maximum fiber stress for the assumed grade a
established by this code in Section 2309.2.2 F’s (“operating” stress) is th
modified allowable maximum fiber stress which may be used in the span table
and for calculating required lumber sizes. F’s is found by multiplying Fs by th
factors given in the table |
- |
pdf_text |
| Note 2 |
Note 2.
Table Columns
Column 1 is the nominal commonly used lumber size
Column 2 is a list of actual sizes of the supplied lumber
Column 2 lists the sizes on the basis of a constant thickness and a width increasing by one
quarter (1/4) inch and one half (1/2) inch
Column 3 gives the multiplier for increasing the assumed allowable stress (Fs) based on th
increases in width as listed in Column 2.
Column 4 gives the multiplier for increasing the assumed allowable stress (Fs) based o
increases in thickness
Example: Fiber stress for assumed grade = one thousand (1,000) psi – Actua
size 3-1/8 x 9-3/4
Nominal size |
- |
pdf_text |
| Note 3 |
Note 3
Therefore, F’s = 1,250 psi is used for calculations and in the span tables
SBC-1 2010
- 30 |
- |
pdf_text |
| SECTION 2702 |
SECTION 2702
EMERGENCY AND STANDBY POWER SYSTEMS |
- |
pdf_text |
| SECTION 3103.0 |
SECTION 3103.0 TEMPORARY STRUCTURES |
- |
pdf_text |
| SECTION 3110.0 |
SECTION 3110.0
FABRIC STRUCTURES |
- |
pdf_text |
| SECTION 424 |
SECTION 424
MANUFACTURED HOMES |
- |
pdf_text |
| SECTION 425 |
SECTION 425
MODULAR CONSTRUCTION |
- |
pdf_text |
| Section 1111.0 |
Section 1111.0 Children’s Features |
- |
pdf_text |
| Section 903.3.1.1.1 |
Section 903.3.1.1.1 Exempt Locations 1-4. Add the following paragraph five (5) |
- |
pdf_text |
| Section 906 |
Section 906 Portable Fire Extinguishers |
- |
pdf_text |
| Section 907 |
Section 907 FIRE ALARM AND DETECTION SYSTEMS |
- |
pdf_text |
| full-text |
SBC-1 2010
- 44
APPENDIX G
FLOOD RESISTANT CONSTRUCTION
Add the following section to G105.1 General
G105.1.1 Notice.
Upon receipt of an application for a variance the Chairman of the Board of Appeals shall
forward a copy of said application to the Rhode Island Emergency Management Office,
Attention: Statewide Flood-Plain Coordinator. |
- |
pdf_text |
| full-text |
Delete IBC 310.1 Residential Group R-3 and R-4 and substitute the following:
R-3 Residential occupancies where the occupants are primarily permanent in
nature and not classified as R-1, R-2, R-4 or I and where buildings do not contain
more than two dwelling units as applicable in Section 101.2, or adult and child
care facilities that provide accommodations for eight or fewer persons of any age
for less than 24 hours. Adult and child care facilities that are within a single-
family home are permitted to comply with the International Residential Code in
accordance with Section 101.2.
R-4 Residential occupancies shall include buildings arranged for occupancy as
residential care/assisted living facilities including more than eight but not more
than 16 occupants, excluding staff.
Group R-4 occupancies shall meet the requirements for construction as defined
for Group R-3 except as otherwise provided for in this code or shall comply with
the International Residential Code in accordance with Section 101.2.
Group R-4 occupancies shall meet the requirements for construction as defined
for Group R-3 except as otherwise provided for in this code or shall comply with
the International Residential Code in accordance with Section 101.2.
Delete IBC 310.2 Definition of Residential Care/Assisted Living Facilities and substitute
the following: |
- |
pdf_text |
| full-text |
CHAPTER 35
REFERENCED STANDARDS
To IBC Chapter 35 add the following General Statement:
The various State of Rhode Island departments and agencies have designated powers to
adopt and enforce regulations impacting new and existing construction. Users of this
code are advised to use all available resources to coordinate the design and approval
process.
SBC-1 2010
- 42 |
- |
pdf_text |
| full-text |
APPENDICES
Delete Appendices A, B, D, J. & K
Retain Appendices C, E, G, H, I.
Appendix F is permitted to be enforced on a discretionary basis by the local building
code official, when in his opinion, existing site and environmental conditions warrant
additional protective measures specified herein.
SBC-1 2010
- 43 |
- |
pdf_text |
| full-text |
STATE OF RHODE ISLAND
BUILDING CODE STANDARDS COMMITTEE
CHAIRMAN
VICE CHAIRMAN
Robert M. Stillings
Architect
Bruce Davey, PE
Structural Engineer
EXECUTIVE COMMITTEE
John Pagliaro
Building Official
William J. Nash, Jr.
Building Official
Bernard J. Bernard, III
Electrical Inspector
Doris Aschman
Public Health Official
William Howe
Fire Official
Alan Durand
Builders Trades Council
Stephen C. Turner, PE
Public Member
Russell Brown
Building Official
Dana Newbrook
Architect
James R. Carlson, RA
Public Member
Michael A. Newman
Master Plumber
G. Thomas Chabot
Electrical Contractor
David F. Palmisciano
Building Trades Council
Randy Collins, Jr., RLA
Landscape Architect
Gordon W. Preiss, PE
Mechanical Engineer
Robert E. DeBlois, Jr.
Builder
Barrie K. Balemian
Builder
Paul DePace, PE
Representative for the Disabled
Vacant
Representative for the Disab
James Fink
Electrical Engineer
John P. Leyden, CBO
State Building Commissio
Executive Secretary
Donald Gagnon
Minimum Housing Inspector
Thomas Coffey
Legal Counsel
SBC-1 2010
- 1 |
- |
pdf_text |
| full-text (cont. 2) |
RESIDENTIAL CARE/ASSISTED LIVING FACILITIES.
A building or part thereof housing a maximum of sixteen persons, on a 24-hour basis,
who because of age, mental disability or other reasons live in a supervised residential
environment which provides personal care services. The occupants are capable of
responding to an emergency situation without physical assistance from staff. This
classification shall include, but not be limited to, the following: residential board and
care facilities, assisted living facilities, halfway houses, group homes, congregate care
facilities, social rehabilitation facilities, alcohol and drug abuse centers and convalescent
facilities. Residential care/assisted living facilities housing more than sixteen persons
shall be classified as a Group I-1.
SBC-1 2010
- 7 |
- |
pdf_text |