| Change | Label | Text |
| added |
6 |
6. Column at Grid C/3 dimensioned 47'-6" from Grid 1 per
existing field conditions -- coordinate with S-101 which
shows column on grid (48'-0"). |
| added |
110 |
110
STAFF BREAKIROOM |
| added |
101 |
101
WAITING /IRECEPTION |
| added |
113 |
113
COL
DIM'D @ 47'-6" FROMIGRID 1 (FIELD VERIFY) |
| added |
103 |
103
RESTROOMI(ACCESSIBLE) |
| added |
3 |
3. See A-102 for life safety / egress plan. |
| added |
5 |
5. Corridor 106 clear width shown 3'-4" (40") -- VERIFY code
minimum for occupant load served (see A-102 egress calc). |
| added |
104 |
104
MECH / ELECIROOM |
| added |
1 |
1. All partitions new 3-5/8" metal stud w/ 5/8" GWB ea. side U.N.O. |
| added |
4400 |
4400 W.
City of Ch
Permit No
Floor
Occupan
Drawn: J.
REVISION
A 06/15/26
N
SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE) |
| added |
40 |
40"ICLR
DOOR SWINGSIINTO CORRIDOR
GENERAL NOTES |
| added |
2 |
2. Existing building shell & structure by others; verify all
dimensions in field prior to fabrication. |
| added |
4 |
4. See S-101 for column and structural grid locations. |
| removed |
7 |
7. See A-102 for the life safety / egress plan and occupant load calculation. |
| removed |
110 |
110 Steril.
ARCHITECTURAL NOTES |
| removed |
9 |
9. See E-101 for Panel EP-1 and EP-2 locations and required clearances relative to these partitions. |
| removed |
3 |
3. The Restroom door (104) is shown swinging outward into Corridor 106 at the point where the corridor is already at its narrowest dimensioned width; coordinate with the electrical engineer, who shows Panel EP-1's required clear working space landing in this same
stretch of corridor on E-101. |
| removed |
5 |
5. All partitions are new 3-5/8" metal stud with 5/8" GWB each side, unless noted otherwise. |
| removed |
1 |
1. Room layout: Vestibule 101 and Waiting/Reception 102 occupy the front (south) portion of the tenant space, adjacent to the primary exit. Office 103 sits opposite Waiting across a shared partition. Restroom 104 (accessible) and Mech/Elec Room 105 occupy the
northeast corner of the front zone. Corridor 106 runs east-west and is the common path of travel connecting Waiting, the four operatories (107-109) and Sterilization (110) at mid-building, back to Staff Break (111), Operatory 4 (112) and Storage (113) at the rear. |
| removed |
8 |
8. See S-101 for column and structural grid locations, including the Grid C/3 column note above. |
| removed |
105 |
105 Mech/Elec |
| removed |
2 |
2. Corridor 106 clear width is shown as 3'-4" (40") between the Waiting/Office partition and the Mech/Elec Room wall. This is the only corridor serving the rear operatories, Sterilization and Break Room, so it carries the full occupant load calculated on A-102; confirm the 40"
clear width against the applicable minimum corridor width for that occupant load before framing. |
| removed |
4 |
4. A column is shown at the Grid C/3 intersection near the Sterilization/Storage partition. This architectural plan dimensions that column at 47'-6" from Grid 1 (field-verify), based on existing field conditions encountered during the walkthrough. The structural framing plan
(S-101) locates the same column strictly on grid, 48'-0" from Grid 1. Reconcile the 6" discrepancy with the structural engineer before any new partition or casework is set relative to this column. |
| removed |
6 |
6. Existing building shell and structure are by others; verify all dimensions in the field prior to fabrication of any new partition or casework. |