Plan Review Copilot
← back to Riverbend Family Dental Clinic
Revision diff

Rev A → Rev B

Riverbend Family Dental Clinic · sheets with no change between these two revisions are omitted

new sheet low_voltage CI-2 — A-102 — Life Safety / Egress Plan 0 unchanged
ChangeLabelText
added 4 4. Emergency/egress lighting along path above per E-101 -- coordinate full-path coverage with electrical engineer.
added 113 113 EGRESS PATH EXIT SEE E-101 FOR EGRESS/EMERGENCY LIGHTING ALONG THIS PATH
added 5 5. Occupant load above is basis for exit signage / panic hardware count; compare to FP-101 hydraulic calc design occupant load.
added 1 1. Corridor 106 serves as common path of travel to Exit at Vestibule 101.
added 4400 4400 W. City of Ch Permit No Life S Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE)
added 2 2. Corridor 106 clear width shown 3'-4" (40") on A-101; confirm against IBC 1020.2 minimum corridor width for occupant load noted above.
added DETAIL 1 DETAIL 1/A-102: EXIT STAIR HANDRAIL HANDRAIL @ 30" AFF (TYP) Ref: guard/handrail height per architectural stair sections OCCUPANT LOAD CALCULATION Business area (offices, waiting, sterilization): 3,400 SF / 100 gross = 34 Clinic / treatment area (operatories, corridor): 3,400... (combined below) Waiting area (concentrated use, 15 net): 480 SF / 15 net = 32 Treatment / clinical support: 1,900 SF / 100 gross = 19 TOTAL OCCUPANT LOAD (this floor) = 85 PERSONS Two means of egress provided; common path of travel and exit access travel distance comply with IBC Table 1006.2.1 / 1017.2 for Group B. EGRESS NOTES
added 104 104 MECH/ELEC
added 3 3. Handrail height at Detail 1/A-102 shown 30" AFF; confirm against IBC 1014.2 / 1011.5.1 handrail height range.