Riverbend Family Dental Clinic · sheets with no change between these two revisions are omitted

new sheet architectural CI-1 — A-101 0 unchanged
ChangeLabelText
added 103 103 RESTROOMI(ACCESSIBLE)
added 4400 4400 W. City of Ch Permit No Floor Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE)
added 40 40"ICLR DOOR SWINGSIINTO CORRIDOR GENERAL NOTES
added 4 4. See S-101 for column and structural grid locations.
added 5 5. Corridor 106 clear width shown 3'-4" (40") -- VERIFY code minimum for occupant load served (see A-102 egress calc).
added 101 101 WAITING /IRECEPTION
added 1 1. All partitions new 3-5/8" metal stud w/ 5/8" GWB ea. side U.N.O.
added 113 113 COL DIM'D @ 47'-6" FROMIGRID 1 (FIELD VERIFY)
added 2 2. Existing building shell & structure by others; verify all dimensions in field prior to fabrication.
added 110 110 STAFF BREAKIROOM
added 3 3. See A-102 for life safety / egress plan.
added 104 104 MECH / ELECIROOM
added 6 6. Column at Grid C/3 dimensioned 47'-6" from Grid 1 per existing field conditions -- coordinate with S-101 which shows column on grid (48'-0").
new sheet civil CI-8 — C-101 — Civil Site Plan 0 unchanged
ChangeLabelText
added 4 4. Existing building setback from front property line to be field-verified; see zoning data table this sheet for required minimum.
added 18 18'-0" WIDE NEW 2" DOMESTIC WATER SERVICE NEW ELEC. SERVICE DUCT BANK UTILITY CROSSING -- NO SEPARATION CALLED OUT (COORD. W/ E-101) ZONING DATA TABLE (DISTRICT B3-2) Front Yard Setback, Required: 25'-0" MIN. Front Yard Setback, Provided (existing bldg.): see dimension this sheet Side Yard Setback, Required: 5'-0" MIN. | Provided: 6'-2" Rear Yard Setback, Required: 20'-0" MIN. | Provided: 24'-0" Max. Lot Coverage: 70% | Provided: 58% Parking Required (B occupancy, 1/300 SF): 14 spaces Parking Provided: 16 spaces (existing lot, restriped) CIVIL / SITE GENERAL NOTES
added 3 3. All site utility work per City of Chicago Dept. of Water Management and ComEd standards, as applicable.
added 2 2. New domestic water service and new electrical service duct bank cross near Sta. 0+20; provide code-required horizontal and vertical separation between utilities -- coordinate with electrical engineer (E-101) and local utility standards.
added 4400 4400 W. City of Ch Permit No Civil S Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1" = 20'-0" (SCHEMATIC, NOT TO SCALE) PROPERTY LINE (TYP.) W. DIVERSEY AVE. (PUBLIC R.O.W.) EXISTING BUILDING (TENANT SUITE 100, THIS PERMIT)
added 18 18'-0" wide; confirm against IFC 503.2.1 min. unobstructed width for fire apparatus access.
added 18 18'-0" TO FACE OF BLDG. FIRE DEPT. ACCESS ROAD
added 1 1. Fire department access road along east property line shown
new sheet electrical CI-5 — E-101 — Electrical Power Plan 0 unchanged
ChangeLabelText
added 4 4. Emergency/egress lighting (fixtures tagged EM) provided along corridor per life safety plan A-102; verify fixture spacing provides continuous coverage along full egress path shown on A-102, including run from Grid 2 to the exit at Vestibule 101.
added 2 2. Panel EP-2 (Mech/Elec Room 105, 120/208V, 30-ckt): dedicated clear working space shown = 2'-6" (30"); NEC 110.26(A)(1) requires 3'-0" (36") minimum clear working space for this voltage-to-ground condition.
added 4 4 A B C D VEST. WAITING OFFICE RR MEC OPER. 1 OPER. 2 OPER. 3 STERIL. BREAK OPER. 4 STORAGE EP-1 REQ'D CLR ZONE OVERLAPS RESTROOM DOOR SWING (SEE A-101) EP DEDICATE CE SHOWN = E 2) EM EM EM EGRESS LTG. FIXTURES END NEAR GRID 2 -- CONFIRM COVERAGE TO EXIT VS. A-102 EGRESS PATH ELECTRICAL GENERAL NOTES
added 3 3. Coordinate Panel EP-2 clearance with plumbing water heater WH-1 location -- see P-101; WH-1 as shown reduces usable clear space in front of EP-2 to approx. 1'-6" (18").
added 5 5. Underground electrical service duct bank -- see C-101 for routing and coordination with site utilities.
added 1 1. Panel EP-1 (Waiting/Office area, 120/208V, 42-ckt): dedicated equipment space per NEC 110.26 required in front of panel; coordinate with adjacent restroom door swing shown on A-101.
added 4400 4400 W. City of Ch Permit No Electri Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE)
new sheet fire_protection CD-7 — FP-101 — Fire Protection (Sprinkler) Plan 0 unchanged
ChangeLabelText
added 2 2. Sprinkler head spacing per NFPA 13 max. coverage area for Light Hazard (225 SF/head) and Ordinary Hazard Group 1 (130 SF/head).
added 3 3. SP-14 (Sterilization 110) location shown at same ceiling grid cell as HVAC supply diffuser D-6 per M-101 -- relocate one device prior to ceiling installation to maintain min. 3'-0" separation and unobstructed spray pattern.
added 4 4 A B C D VEST. WAITING OFFICE RR MECH/ELEC OPER. 1 OPER. 2 OPER. 3 STERIL. BREAK OPER. 4 STORAGE SP-1 SP-2 SP-3 SP-4 SP-9 SP-10 SP-11 SP-14 SP-17 SP-18 SP-19 SP-14 SHARES CEILING GRID CELL WITH SUPPLY DIFFUSER D-6 (SEE M-101) FIRE PROTECTION GENERAL NOTES
added 4400 4400 W. City of Ch Permit No Fire Pr Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE)
added 4 4. Exit signage and panic hardware quantities per Design Occupant Load noted below; confirm against A-102 Life Safety occupant load calculation. HYDRAULIC CALCULATION / DESIGN BASIS Design Occupant Load (this floor) = 60 PERSONS (per approved space program, used for exit sign / panic hardware quantities and hydraulic demand basis) Design Density: 0.10 gpm/sf over 1,500 sf (Light Hazard) Required Flow: 225 gpm @ 15 psi residual (est.) Water Supply: Existing 6" combined main, per test 6/2026
added 1 1. System: wet-pipe automatic sprinkler, NFPA 13, Light Hazard occupancy classification throughout, Ordinary Hazard Group 1 at Sterilization 110.
new sheet plumbing CI-6 — P-101 — Plumbing Plan 0 unchanged
ChangeLabelText
added 3 3"W/2"V Mech/Elec Rm. S Sink, clinical hand-wash
added 4400 4400 W. City of Ch Permit No Plumb Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE)
added 1 1. WH-1: 50-gal. gas-fired water heater, set on 18" stand, located in Mech/Elec Room 105 per plan.
added 2 2. WH-1 clearance from east wall shown = 1'-6" (18"); coordinate with Electrical Panel EP-2 dedicated equipment space shown on E-101 (36" min. required per NEC 110.26(A)(1)) -- WH-1 as located reduces available clear floor space in front of EP-2.
added 1-1 1-1/2"W ADA compliant MS Mop Sink
added 4 4 A B C D VEST. WAITING OFFICE RR MECH/ELEC OPER. 1 OPER. 2 OPER. 3 STERIL. BREAK OPER. 4 STORAGE WH-1 WH-1 SET 1'-6" CLR FROM E. WALL -- VERIFY ELEC. PANEL EP-2 CLEARANCE (E-101) WC LAV MS S S S S PLUMBING GENERAL NOTES
added 3 3"W/2"V ADA compliant LAV Lavatory, wall hung
added 1-1 1-1/2"W Each operatory WH-1 Water Heater, 50-gal gas
added 5 5. Fixture units and pipe sizing per fixture schedule, this sheet. Tag Fixture Conn. Notes WC Water Closet, tank type
added 3 3/4" CW/HW See note 1-2
added 3 3. T&P relief valve discharge piped full size to within 6" of floor per IPC / manufacturer's instructions.
added 4 4. All waste and vent piping PVC DWV; domestic water piping Type L copper, U.N.O.