| Change | Label | Text |
|---|---|---|
| added | 103 | 103 RESTROOMI(ACCESSIBLE) |
| added | 4400 | 4400 W. City of Ch Permit No Floor Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE) |
| added | 40 | 40"ICLR DOOR SWINGSIINTO CORRIDOR GENERAL NOTES |
| added | 4 | 4. See S-101 for column and structural grid locations. |
| added | 5 | 5. Corridor 106 clear width shown 3'-4" (40") -- VERIFY code minimum for occupant load served (see A-102 egress calc). |
| added | 101 | 101 WAITING /IRECEPTION |
| added | 1 | 1. All partitions new 3-5/8" metal stud w/ 5/8" GWB ea. side U.N.O. |
| added | 113 | 113 COL DIM'D @ 47'-6" FROMIGRID 1 (FIELD VERIFY) |
| added | 2 | 2. Existing building shell & structure by others; verify all dimensions in field prior to fabrication. |
| added | 110 | 110 STAFF BREAKIROOM |
| added | 3 | 3. See A-102 for life safety / egress plan. |
| added | 104 | 104 MECH / ELECIROOM |
| added | 6 | 6. Column at Grid C/3 dimensioned 47'-6" from Grid 1 per existing field conditions -- coordinate with S-101 which shows column on grid (48'-0"). |
| Change | Label | Text |
|---|---|---|
| added | 4 | 4. Existing building setback from front property line to be field-verified; see zoning data table this sheet for required minimum. |
| added | 18 | 18'-0" WIDE NEW 2" DOMESTIC WATER SERVICE NEW ELEC. SERVICE DUCT BANK UTILITY CROSSING -- NO SEPARATION CALLED OUT (COORD. W/ E-101) ZONING DATA TABLE (DISTRICT B3-2) Front Yard Setback, Required: 25'-0" MIN. Front Yard Setback, Provided (existing bldg.): see dimension this sheet Side Yard Setback, Required: 5'-0" MIN. | Provided: 6'-2" Rear Yard Setback, Required: 20'-0" MIN. | Provided: 24'-0" Max. Lot Coverage: 70% | Provided: 58% Parking Required (B occupancy, 1/300 SF): 14 spaces Parking Provided: 16 spaces (existing lot, restriped) CIVIL / SITE GENERAL NOTES |
| added | 3 | 3. All site utility work per City of Chicago Dept. of Water Management and ComEd standards, as applicable. |
| added | 2 | 2. New domestic water service and new electrical service duct bank cross near Sta. 0+20; provide code-required horizontal and vertical separation between utilities -- coordinate with electrical engineer (E-101) and local utility standards. |
| added | 4400 | 4400 W. City of Ch Permit No Civil S Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1" = 20'-0" (SCHEMATIC, NOT TO SCALE) PROPERTY LINE (TYP.) W. DIVERSEY AVE. (PUBLIC R.O.W.) EXISTING BUILDING (TENANT SUITE 100, THIS PERMIT) |
| added | 18 | 18'-0" wide; confirm against IFC 503.2.1 min. unobstructed width for fire apparatus access. |
| added | 18 | 18'-0" TO FACE OF BLDG. FIRE DEPT. ACCESS ROAD |
| added | 1 | 1. Fire department access road along east property line shown |
| Change | Label | Text |
|---|---|---|
| added | 4 | 4. Emergency/egress lighting (fixtures tagged EM) provided along corridor per life safety plan A-102; verify fixture spacing provides continuous coverage along full egress path shown on A-102, including run from Grid 2 to the exit at Vestibule 101. |
| added | 2 | 2. Panel EP-2 (Mech/Elec Room 105, 120/208V, 30-ckt): dedicated clear working space shown = 2'-6" (30"); NEC 110.26(A)(1) requires 3'-0" (36") minimum clear working space for this voltage-to-ground condition. |
| added | 4 | 4 A B C D VEST. WAITING OFFICE RR MEC OPER. 1 OPER. 2 OPER. 3 STERIL. BREAK OPER. 4 STORAGE EP-1 REQ'D CLR ZONE OVERLAPS RESTROOM DOOR SWING (SEE A-101) EP DEDICATE CE SHOWN = E 2) EM EM EM EGRESS LTG. FIXTURES END NEAR GRID 2 -- CONFIRM COVERAGE TO EXIT VS. A-102 EGRESS PATH ELECTRICAL GENERAL NOTES |
| added | 3 | 3. Coordinate Panel EP-2 clearance with plumbing water heater WH-1 location -- see P-101; WH-1 as shown reduces usable clear space in front of EP-2 to approx. 1'-6" (18"). |
| added | 5 | 5. Underground electrical service duct bank -- see C-101 for routing and coordination with site utilities. |
| added | 1 | 1. Panel EP-1 (Waiting/Office area, 120/208V, 42-ckt): dedicated equipment space per NEC 110.26 required in front of panel; coordinate with adjacent restroom door swing shown on A-101. |
| added | 4400 | 4400 W. City of Ch Permit No Electri Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE) |
| Change | Label | Text |
|---|---|---|
| added | 2 | 2. Sprinkler head spacing per NFPA 13 max. coverage area for Light Hazard (225 SF/head) and Ordinary Hazard Group 1 (130 SF/head). |
| added | 3 | 3. SP-14 (Sterilization 110) location shown at same ceiling grid cell as HVAC supply diffuser D-6 per M-101 -- relocate one device prior to ceiling installation to maintain min. 3'-0" separation and unobstructed spray pattern. |
| added | 4 | 4 A B C D VEST. WAITING OFFICE RR MECH/ELEC OPER. 1 OPER. 2 OPER. 3 STERIL. BREAK OPER. 4 STORAGE SP-1 SP-2 SP-3 SP-4 SP-9 SP-10 SP-11 SP-14 SP-17 SP-18 SP-19 SP-14 SHARES CEILING GRID CELL WITH SUPPLY DIFFUSER D-6 (SEE M-101) FIRE PROTECTION GENERAL NOTES |
| added | 4400 | 4400 W. City of Ch Permit No Fire Pr Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE) |
| added | 4 | 4. Exit signage and panic hardware quantities per Design Occupant Load noted below; confirm against A-102 Life Safety occupant load calculation. HYDRAULIC CALCULATION / DESIGN BASIS Design Occupant Load (this floor) = 60 PERSONS (per approved space program, used for exit sign / panic hardware quantities and hydraulic demand basis) Design Density: 0.10 gpm/sf over 1,500 sf (Light Hazard) Required Flow: 225 gpm @ 15 psi residual (est.) Water Supply: Existing 6" combined main, per test 6/2026 |
| added | 1 | 1. System: wet-pipe automatic sprinkler, NFPA 13, Light Hazard occupancy classification throughout, Ordinary Hazard Group 1 at Sterilization 110. |
| Change | Label | Text |
|---|---|---|
| added | 3 | 3"W/2"V Mech/Elec Rm. S Sink, clinical hand-wash |
| added | 4400 | 4400 W. City of Ch Permit No Plumb Occupan Drawn: J. REVISION A 06/15/26 N SCALE: 1/8" = 1'-0" (SCHEMATIC, NOT TO SCALE) |
| added | 1 | 1. WH-1: 50-gal. gas-fired water heater, set on 18" stand, located in Mech/Elec Room 105 per plan. |
| added | 2 | 2. WH-1 clearance from east wall shown = 1'-6" (18"); coordinate with Electrical Panel EP-2 dedicated equipment space shown on E-101 (36" min. required per NEC 110.26(A)(1)) -- WH-1 as located reduces available clear floor space in front of EP-2. |
| added | 1-1 | 1-1/2"W ADA compliant MS Mop Sink |
| added | 4 | 4 A B C D VEST. WAITING OFFICE RR MECH/ELEC OPER. 1 OPER. 2 OPER. 3 STERIL. BREAK OPER. 4 STORAGE WH-1 WH-1 SET 1'-6" CLR FROM E. WALL -- VERIFY ELEC. PANEL EP-2 CLEARANCE (E-101) WC LAV MS S S S S PLUMBING GENERAL NOTES |
| added | 3 | 3"W/2"V ADA compliant LAV Lavatory, wall hung |
| added | 1-1 | 1-1/2"W Each operatory WH-1 Water Heater, 50-gal gas |
| added | 5 | 5. Fixture units and pipe sizing per fixture schedule, this sheet. Tag Fixture Conn. Notes WC Water Closet, tank type |
| added | 3 | 3/4" CW/HW See note 1-2 |
| added | 3 | 3. T&P relief valve discharge piped full size to within 6" of floor per IPC / manufacturer's instructions. |
| added | 4 | 4. All waste and vent piping PVC DWV; domestic water piping Type L copper, U.N.O. |