| Type | Severity | Sheet / Clause | Finding | Cited | Model | Revision | Timestamp |
|---|---|---|---|---|---|---|---|
| cross-discipline | high | structural S-101 / 1.1 | The structural beam B-4 in Corridor 104 provides a minimum clear height of 9 feet 0 inches, but the ductwork DS-2 in the same corridor requires a minimum clearance of 9 feet 6 inches, which is physically incompatible. |
mechanical 1.1
|
llama-3.3-70b-versatile | Rev A | 2026-07-22 04:49 |
| cross-discipline | high | mechanical M-101 / 1.1 | The mechanical clause requires a minimum clearance of 9 feet 6 inches, while the structural clause provides a minimum clear height of 9 feet 0 inches within the same corridor, Corridor 104, creating a physically incompatible condition. |
structural 1.1
|
llama-3.3-70b-versatile | Rev A | 2026-07-22 04:49 |
| cross-discipline | high | architectural A-102 / 1.1 | The 36 inch swing radius of Door D-12 centered 6 inches off the north wall in Electrical Room 118 is physically incompatible with the required 36 inch clear working space in front of Panel EP-3, also mounted on the north wall in the same room. |
electrical 1.1
|
llama-3.3-70b-versatile | Rev A | 2026-07-22 04:49 |
| vs. code | medium | electrical E-101 / 1.1 |
[SIMULATED - keyword heuristic, not real reasoning] This clause and the closest matching code section (3) both state numeric requirements, but the numbers don't match: this clause says 118, 3, 36, the code section says 1829. Worth a closer look to confirm whether this is a real conflict.
(simulated - keyword heuristic, not model reasoning) |
3
|
mock-keyword-heuristic | Rev A | 2026-07-22 04:49 |
| vs. code | medium | electrical E-101 / 1.2 |
[SIMULATED - keyword heuristic, not real reasoning] This clause and the closest matching code section (3) both state numeric requirements, but the numbers don't match: this clause says 121, 36, 6, the code section says 1829. Worth a closer look to confirm whether this is a real conflict.
(simulated - keyword heuristic, not model reasoning) |
3
|
mock-keyword-heuristic | Rev A | 2026-07-22 04:49 |
| vs. code | medium | architectural A-102 / 1.1 |
[SIMULATED - keyword heuristic, not real reasoning] This clause and the closest matching code section (10) both state numeric requirements, but the numbers don't match: this clause says 118, 12, 36, 6, the code section says 000, 1006.2, 2.7, 3. Worth a closer look to confirm whether this is a real conflict.
(simulated - keyword heuristic, not model reasoning) |
10
|
mock-keyword-heuristic | Rev A | 2026-07-22 04:49 |
| cross-discipline | medium | electrical E-101 / 1.1 | The required 36 inch clear working space per NEC in front of Panel EP-3 in Electrical Room 118 interferes with the 36 inch swing radius of Door D-12, which swings into the same room and is centered 6 inches off the north wall where the panel is mounted. |
architectural 1.1
|
llama-3.3-70b-versatile | Rev A | 2026-07-22 04:49 |
| cross-discipline | medium | architectural A-102 / 1.2 | Door D-15 swings outward into the corridor, which may conflict with the required 36 inch clear working space for Panel EP-6 in Electrical Room 121. |
electrical 1.2
|
llama-3.3-70b-versatile | Rev A | 2026-07-22 04:49 |