Plan Review Copilot
← back to Demo: Data Center Campus (Full Set)
Flags

Current flags — Demo: Data Center Campus (Full Set)

Every clause is only ever reasoned about once per check type - a flag found under an earlier revision stays current here until the clause it's about is itself superseded by a later revision, not until the whole project is re-checked.
12 high 4 medium 4 low
cross-discipline · Electrical Conduit & Cable Tray Routing (Demo) open
Explanation

Both the electrical cable tray CT-5 (at 3'6" AFF) and the low-voltage BMS backbone cabling tray (at 3'0" AFF) are routed through Electrical Room 210 and both intersect the switchgear SG-2 required working clearance zone (per NEC 110.26, this space must remain unobstructed). Two trays at nearly the same elevation both crossing the dedicated clearance envelope for SG-2 represent a physical space conflict - the working clearance cannot be encroached by either tray, and their close vertical proximity (6 inches apart) also raises installation/clash risk.

Cited
low_voltage 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Civil Site Utilities & Grading (Demo) open
Explanation

The utility trench for the electrical duct bank at column line 12 is excavated to 4'-0" below finished grade, which is deeper than Footing F-12's bearing depth of 3'-6" below finished grade at the same column line. Excavating the trench below the footing's bearing elevation could undermine the footing's bearing soil, creating a structural conflict unless special shoring, underpinning, or sequencing is specified.

Cited
structural 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Architectural Reflected Ceiling Plan (Demo) open
Explanation

Architectural clause 1.2 requires a minimum 8'-6" clear from finished floor to the underside of any overhead equipment in Data Hall 4. Mechanical clause 2.1 places exhaust louver EL-3 penetrating the Data Hall 4 exterior wall at only 7'-6" above finished floor, which is 1'-0" below the required minimum clearance, creating a direct conflict.

Cited
mechanical 2.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Architectural Egress & Room Layout (Demo) open
Explanation

Door D-21 swings inward into Electrical Room 210 with a 42-inch arc centered 8 inches off the west wall. Switchgear SG-2, located in the same room, requires a dedicated 42-inch deep working clearance per NEC 110.26 that must remain free of any other trade's infrastructure, including obstructions like door swings. If the door's swing arc overlaps the required clearance zone in front of SG-2, this violates the code-mandated clear working space.

Cited
electrical 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Structural Steel Framing & Beams (Demo) open
Explanation

Structural beam B-14 limits clear height in Data Hall 2 to 14'0" AFF, but mechanical ductwork DS-11 in the same space requires clearance to 14'6" AFF to the bottom of duct insulation. The duct clearance requirement exceeds the available clear height under the beam, making the two requirements physically incompatible.

Cited
mechanical 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Low Voltage Structured Cabling & BMS (Demo) open
Explanation

The BMS backbone cabling tray is routed at 3'-0" AFF through Electrical Room 210, placing it within the SG-2 working clearance zone. Electrical clause b88a0614 requires this working clearance to be kept dedicated and free of any other trade's infrastructure per NEC 110.26. Additionally, electrical clause 9bbd319b already places Cable Tray CT-5 at 3'-6" AFF crossing this same clearance zone, meaning both the low-voltage BMS tray and CT-5 encroach into the same protected clearance space, compounding the NEC violation and creating a potential physical clash between the two trays themselves.

Cited
electrical 1.1, electrical 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Structural Foundation & Footings (Demo) open
Explanation

Footing F-12 at column line 12 bears at 3'-6" below finished grade, which is shallower than the adjacent electrical duct bank trench along the same column line excavated to 4'-0" below finished grade. Excavating the utility trench deeper than and adjacent to the footing bearing elevation risks undermining the footing's bearing soil, requiring coordination (e.g., trench location offset, underpinning, or lowering the footing bearing elevation).

Cited
civil 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Fire Protection Sprinkler & Standpipe (Demo) open
Explanation

Sprinkler branch line SP-6 is located at 14'-3" AFF in Data Hall 2, which is below the 14'-6" AFF clearance required for the bottom of DS-11 duct insulation in the same space. This places the sprinkler line within the mandated clear zone beneath the duct insulation, creating a physical clash/coordination conflict.

Cited
mechanical 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Mechanical CRAC Unit Layout (Demo) open
Explanation

Mechanical clause routes condenser water piping at 7'-0" AFF along the Data Hall 1 perimeter wall, but the architectural RCP for Data Hall 1 requires a minimum 9'-0" clear from finished floor to the underside of any overhead equipment, duct, tray, or pipe. The piping height violates the required clearance.

Cited
architectural 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Mechanical Ductwork & Louvers (Demo) open
Explanation

Ductwork DS-11 in Data Hall 2 requires 14'-6" clearance to bottom of duct insulation, but structural beam B-14 only provides 14'-0" clear height in Data Hall 2. The duct clearance requirement exceeds the available structural clear height by 6 inches, making it physically impossible to install as specified.

Cited
structural 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Mechanical Ductwork & Louvers (Demo) open
Explanation

Sprinkler branch line SP-6 crosses Data Hall 2 at 14'-3", which is below the 14'-6" minimum clearance required for the bottom of DS-11 duct insulation. This indicates a direct physical clash between the sprinkler line and the ductwork/insulation envelope in the same space.

Cited
fire_protection 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Electrical Switchgear & Panel Layout (Demo) open
Explanation

The low_voltage cable tray for the BMS backbone runs at 3'-0" AFF through Electrical Room 210 directly within the SG-2 working clearance zone required by NEC 110.26 to be a dedicated 42-inch deep space free of other trades' infrastructure. This is a direct physical conflict.

Cited
low_voltage 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Civil Site Utilities & Grading (Demo) open
Explanation

Civil clause specifies the utility trench for the domestic water tie-in at column line 18 excavated to only 3'-0" below finished grade, but the plumbing domestic water main entry is specified at 4'-0" below finished grade. The trench depth does not match the depth of the pipe it is intended to receive, creating a coordination discrepancy.

Cited
plumbing 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Structural Foundation & Footings (Demo) open
Explanation

Footing F-18 at column line 18 bears at 5'0" below finished grade, while the civil site utility trench along the same column line 18 is excavated to 3'0" below finished grade for a domestic water tie-in. Although the trench is shallower than the footing bearing elevation, the trench runs along the same column line and could be located close enough horizontally to undermine the footing's bearing soil if not properly offset or if excavation encroaches within the footing's influence zone. This requires coordination to confirm horizontal separation and that the trench does not undercut the footing's bearing stratum.

Cited
civil 1.2
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Plumbing Domestic Water & Drainage (Demo) open
Explanation

Plumbing clause states the domestic water main enters the building 4'-0" below finished grade, but the civil site utility trench specifically excavated for the domestic water tie-in (clause 1.2) is only excavated to 3'-0" below finished grade. The trench depth does not match the specified depth of the incoming water main, creating a potential conflict in bury depth/elevation coordination.

Cited
civil 1.2
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Mechanical Ductwork & Louvers (Demo) open
Explanation

Exhaust louver EL-3 is mounted at 7'-6" AFF in Data Hall 4, which is below the 8'-6" minimum clear height required by the architectural RCP for Data Hall 4 from finished floor to the underside of any overhead equipment, duct, tray, or pipe. This places the louver within the required clear zone, conflicting with the ceiling clearance requirement.

Cited
architectural 1.2
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Civil Site Utilities & Grading (Demo) open
Explanation

The trench at column line 18 is excavated to 3'-0" below finished grade, which is above (shallower than) the 5'-0" bearing depth of adjacent Footing F-18 at the same column line. While this may be acceptable depending on lateral offset, if the trench is close to the footing it could undermine the footing's bearing soil, requiring coordination on trench location/shoring relative to the footing.

Cited
structural 1.2
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Mechanical CRAC Unit Layout (Demo) open
Explanation

Mechanical clause requires only 8'6" overhead clearance for CRAC unit CU-6 in Data Hall 1, while the architectural RCP for Data Hall 1 requires a minimum 9'0" clear from finished floor to the underside of any overhead equipment. Although CU-6's requirement does not itself violate the 9'0" minimum (8'6" is less than 9'0"), the two clauses reference different clearance values for the same room and equipment type, which should be confirmed as consistent (i.e., CU-6 must not be installed such that its top clears at less than 9'0", verifying no conflict in final installed height).

Cited
architectural 1.1
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Mechanical CRAC Unit Layout (Demo) open
Explanation

Mechanical clause 1.2 requires only 7'0" of overhead clearance for CRAC unit CU-9 in Data Hall 4, which is less than the 8'6" clear height mandated by the architectural RCP for Data Hall 4. This is not a true conflict since the mechanical requirement is a minimum, not a maximum, and 7'0" fits within the 8'6" envelope, but it is flagged for coordination confirmation that CU-9's actual installed height does not exceed the architectural clearance limit.

Cited
architectural 1.2
Model
claude-sonnet-5 view reasoning
Status
cross-discipline · Electrical Switchgear & Panel Layout (Demo) open
Explanation

Door D-21 swings inward into Electrical Room 210 with a 42-inch arc centered 8 inches off the west wall; depending on the location of SG-2 and the direction of its required working clearance, the door swing could intrude into the dedicated 42-inch clearance zone, which must remain free of obstructions. This should be verified against the switchgear's exact position and clearance direction.

Cited
architectural 1.1
Model
claude-sonnet-5 view reasoning
Status