Flags

Current flags — Demo: Cross-Discipline Clash Set

Every clause is only ever reasoned about once per check type - a flag found under an earlier revision stays current here until the clause it's about is itself superseded by a later revision, not until the whole project is re-checked.
3 high 1 medium 0 low
vs. code · Electrical Panel & Clearance Notes (Demo) open
Explanation

The project clause specifies only 36 inches of clear working space in front of Panel EP-3, but the jurisdiction's local amendment requires a six foot (1829 mm) clear working space in front of all panels, regardless of the NEC's typically smaller minimum. This is a direct conflict since 36 inches is less than the required 72 inches.

Cited
3
Model
claude-sonnet-5 view reasoning
Status
vs. code · Electrical Panel & Clearance Notes (Demo) open
Explanation

The project clause specifies only 36 inches (3 feet) of clear working space in front of Panel EP-6, but the local amendment (clause 3) requires a minimum of six feet (1829 mm) of clear working space in front of all panels, superseding the standard NEC minimum. The project clause's 36-inch allowance does not meet this jurisdiction-specific requirement.

Cited
3
Model
claude-sonnet-5 view reasoning
Status
vs. code · Electrical Panel & Clearance Notes (Demo) open
Explanation

The project clause locates Panel EP-6 within a dedicated Electrical Room (Room 121), but the local amendment (clause 2) prohibits panels from being located in a separate room.

Cited
2
Model
claude-sonnet-5 view reasoning
Status
vs. code · Electrical Panel & Clearance Notes (Demo) open
Explanation

The project clause states Panel EP-3 is located in Electrical Room 118, implying it is situated in a separate, dedicated electrical room. The local amendment prohibits panels from being located in a separate room, creating a potential conflict if Room 118 is a dedicated electrical room solely for housing panels.

Cited
2
Model
claude-sonnet-5 view reasoning
Status