| Type | Severity | Clause | Found in | Explanation | Cited | Model | Status | |
|---|---|---|---|---|---|---|---|---|
| cross-discipline | high | 1.1 | Rev A | The structural beam B-4 in Corridor 104 provides a minimum clear height of 9 feet 0 inches, but the ductwork DS-2 in the same corridor requires a minimum clearance of 9 feet 6 inches, which is physically incompatible. |
mechanical 1.1
|
llama-3.3-70b-versatile | view reasoning | |
| cross-discipline | high | 1.1 | Rev A | The mechanical clause requires a minimum clearance of 9 feet 6 inches, while the structural clause provides a minimum clear height of 9 feet 0 inches within the same corridor, Corridor 104, creating a physically incompatible condition. |
structural 1.1
|
llama-3.3-70b-versatile | view reasoning | |
| cross-discipline | high | 1.1 | Rev A | The 36 inch swing radius of Door D-12 centered 6 inches off the north wall in Electrical Room 118 is physically incompatible with the required 36 inch clear working space in front of Panel EP-3, also mounted on the north wall in the same room. |
electrical 1.1
|
llama-3.3-70b-versatile | view reasoning | |
| cross-discipline | medium | 1.1 | Rev A | The required 36 inch clear working space per NEC in front of Panel EP-3 in Electrical Room 118 interferes with the 36 inch swing radius of Door D-12, which swings into the same room and is centered 6 inches off the north wall where the panel is mounted. |
architectural 1.1
|
llama-3.3-70b-versatile | view reasoning | |
| cross-discipline | medium | 1.2 | Rev A | Door D-15 swings outward into the corridor, which may conflict with the required 36 inch clear working space for Panel EP-6 in Electrical Room 121. |
electrical 1.2
|
llama-3.3-70b-versatile | view reasoning |